D5264S G.M. International s.r.l.
GM International

D5264S
I.S. SIL2 Load Cell/Strain Gauge Bridge Converter

The Load Cell/Strain Gauge Bridge Converter D5264 module is a unit suitable for applications requiring SIL 2 level in safety related systems for high risk industries. The unit acts as a galvanically isolated interface installed between a PLC/DCS in Safe Area and a load cell (or a group of load cells) in Hazardous Area. Up to four 350 Ω load cells, or five 450 Ω load cells, or ten 1000 Ω load cells can be connected in parallel. It provides a fully floating power supply voltage with remote sensing capabilities to load cells located in Hazardous Area and converts the mV signal from the load cell into a 0/4-20 mA, providing both current source and sink capabilities. The module is also provided with PhotoMOS alarm output. A modbus output is also provided to interface the PLC/DCS using digital communication.

FEATURES

  • SIL 2 / SC 3
  • Input from Zone 0
  • Installation in Zone 2
  • Strain Gauge Bridge Isolated Converter
  • Up to four 350 Ω load cells in parallel
  • 0/4-20 mA sink/source output current
  • Modbus RTU RS-485 for monitor & configuration
  • Field Automatic Calibration
  • Fully programmable operating parameters
  • High Accuracy, μP controlled A/D converter
  • Three port isolation, Input/Output/Supply

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

1

Request a free and personalized quotation!

Technical Data


Supply

Type 24 Vdc nom (18 to 30 Vdc), reverse polarity protected.
Current Consumption 90 mA @ 24 Vdc with four 350 Ω load cells connected and 20 mA output, typical.
Power Dissipation 2.1 W @ 24 Vdc with four 350 Ω load cells connected and 20 mA output, typical.

Input

Type Up to four 350 Ω load cells (parallel connection). up to five 450 Ω load cells (parallel connection). up to ten 1000 Ω load cells (parallel connection).
Integration time 100 ms (slow) or 12.5 ms (fast).
Bridge supply voltage 4.0 Vdc nominal.
Bridge output signal 1 to 4 mV/V.

Output

Type 0/4 to 20 mA, on max. 400 Ω load, current limited @ 24 mA.
Response time ≤ 20 ms (10 to 90 % step).

Alarm

Trip point range within rated limits of the input sensor.
ON-OFF delay time 0 to 1000 s, 100 ms step.
Hysteresis within rated limits of input sensor.
Output voltage free SPST photoMOS: 100 mA, 60 Vdc (≤ 1 V drop).

Modbus interface

Type Modbus RTU RS-485 up to 115.2 kbps for monitor/configuration/control.

Input performance

Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
Calibration accuracy ≤ ± 0.05 % FSR.
Linearity accuracy ≤ ± 0.02 % FSR.
Temp. influence ≤ ± 0.002 % FSR for a 1 °C change.

Output performance

Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
Calibration accuracy ≤ ± 0.05 % FS.
Linearity accuracy ≤ ± 0.05 % FS.
Temp. influence ≤ ± 0.01 % FS on zero/span for a 1 °C change.

Isolation

Test Voltage I.S. In/Out 2.5 kV; I.S. In/Modbus Out 2.5 kV; I.S. In/Supply 2.5 kV; Out/Supply 500 V; Modbus Out/Supply 500 V; Out/Modbus Out 500 V; Out/Alarm Out 500 V; Alarm Out/Modbus Out 500 V; Supply/Alarm Out 500 V.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Storage temperature temperature limits –45 to +80 °C.

Safety description

Equipment Associated apparatus and non-sparking electrical equipment.
Safety parameters Uo = 7.2 V, Io = 177 mA, Po = 471 mW at terminals 13-14-15-16-17-18. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70°C.

Mounting

Type DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board.
Weight about 160 g.
Connection by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm² (13 AWG).
Dimensions Width 22.5 mm, Depth 123 mm, Height 120 mm.

Data Sheet


Datasheet of D5264 ( EN | RU | CN | FR | JA | IT | ES | DE | PT )

Instruction Manual


Instruction Manual D5264S ( EN )
Instruction Manual D5000-D5200 Series ( EN )
Instruction Manual SWC5090 ( EN | RU )
Safety Manual D5264S ( EN )
ATEX safety instruction manual for D5000 series ( EN | IT )
CCC Ex safety instruction manual for D5000 series ( EN | CN )
Ex safety instruction manual for D5000 series ( RU )

Certifications


Type Description Area Number Issued by Issue Date
ATEX TUV NORD ATEX D5263S, D5264S Series English Certificate ( EN ) Europe TUV 15 ATEX 170897 X TUV_NORD 2020-11-13
EMC D5000/D6000 EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.АЖ38.В.00126/19 EUROCERT 2019-05-31
Ex D5000 CCC certificate for China ( EN ) China 2020322316000978 NEPSI 2024-03-22
Ex CML D5263, D5264 certificate for Japan ( EN ) Japan CML 20JPN2136X CML 2023-07-02
Ex EAC Ex Certificate for D5000 Series ( RU ) Eurasian Community ЕАЭС RU С-IT.ЕХ01.В.00018/19 CCVE 2019-04-25
Ex Emirates Certificate of Conformity D5263, D5264 series ( EN ) United Arab Emirates 23-11-90981/E23-11-094134/NB0002 SGS 2023-11-07
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
IECEx TUV NORD IECEx D5263S, D5264S Series English Certificate ( EN ) International IECEx TUN 16.0005X TUV_NORD 2020-11-13
Maritime KR Maritime Certificate D5000 Series ( EN ) International MIL20769-EL002 KR 2020-10-12
Metrological Metrological Certificate Belarus for D5000/D6000 Series ( BE ) Belarus 15507 ROSSTANDART 2022-08-30
Metrological Metrological Certificate Kazakhstan for D5000/D6000 series ( KK ) Kazakhstan 1152 KMC 2021-08-05
Metrological Metrological Certificate Russia for D5000/D6000 series ( RU ) Russia OC.C.32.004.A n. 77881 ROSSTANDART 2020-07-28
SIL TUV C-IS-722160171 SIL Certificate Summary ( EN ) International C-IS-722160171 TUV_SUD 2022-10-14

Declarations of Conformity


EU Declaration of Conformity for D5263, D5264 ( EN | IT )
EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
Declaration of Conformity G3 compliance ( EN )

Dimensions


Image of D5264_size

Connections


Drawings


2d_drawing_D5200_dwg ( EN )
3d_drawing_D5200_dwg ( EN )
3d_drawing_D5200_stp ( EN )

Software


SWC5090 - Configurator for D5000/D5200, D6000/D6200 Series isolators ( EN )
Instruction Manual SWC5090 ( EN )