D1048S G.M. International s.r.l.
GM International

D1048S
SIL 3 Digital Output Driver, NE Loads, Loop Powered, DIN-Rail

The single channel DIN-Rail Loop Powered Digital Output Isolator, D1048S, is suitable for driving solenoid valves, visual or audible alarms to alert a plant operator, or other process control devices in Hazardous Area from a driving signal in Safe Area. It can also be used as a controllable supply to power measuring or process control equipment. Its use is allowed in applications requiring up to SIL 3 level (according to IEC 61508:2010 Ed. 2) in safety related systems for high risk industries. The Safety PLC or DCS driving signal powers the field device through the D1048S, which provides isolation and is capable of monitoring the conditions of the line. Short and open circuit diagnostic monitoring, dip-switch selectable and active when input power is present, provides LED indication and NC transistor output signaling. When fault is detected output is de-energized until normal condition is restored. Line short and open output circuit fault detection is also reflected on the PLC / DCS input circuit providing less than 10 mA consumption. An override input, dip-switch selectable, is provided to permit a safety system to override the control signal. When enabled, a low input voltage always de-energizes the field device regardless of the input signal. Three basic output circuits are selectable, with different safety parameters, to interface the majority of devices on the market. The selection among the three output characteristics is obtained by connecting the field device to a different terminal block.

FEATURES

  • SIL3/SC3
  • Output to Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
  • Loop powered for NE loads.
  • Short and open circuit line diagnostic monitoring with LED, transistor output and current level on input.
  • Output short circuit proof and current limited
  • Three port isolation, Input/Output/Fault.
  • EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1.
  • In-field programmability by DIP Switch.
  • 250 Vrms (Um) max. voltage allowed to the Instruments associated with the barrier.

STATUS

 
   SPARE-ONLY
Next: OBSOLETE (2025-12-31)

Product lifecycle policy (EN)

ALTERNATIVE PRODUCT

CHANNELS

1

Request a free and personalized quotation!

Technical Data


Loop Input

Type loop powered control signal.
Supply 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, 2 A time lag fuse internally protected. Supplies also diagnostic monitoring control circuit.
Current Consumption 65 mA @ 24 V with 45 mA output typical in normal operation, ≤ 10 mA when fault circuit enabled and fault condition detected.
Power Dissipation 1.1 W with 24 V supply, output energized at 45 mA nominal load.
Max. power consumption at 30 V supply voltage, 1.8 W.

Override Input

Type override control signal de-energizes output when enabled by dip-switch.
Range 24 Vdc nom (20 to 30 Vdc) to disable (field device controlled by input), 0 to 5 Vdc to de-energize field device, reverse polarity protected.
Current Consumption 5 mA @ 24 V.

Output

Type 45 mA at 13.0 V (21.0 V no load, 174 Ω series resistance) at terminals 13-16 Out A. 45 mA at 10.2 V (21.0 V no load, 236 Ω series resistance) at terminals 14-16 Out B. 45 mA at 8.5 V (21.0 V no load, 275 Ω series resistance) at terminals 15-16 Out C.
Short circuit current ≥ 50 mA (55 mA typical).
Response time 75 ms.

Fault detection

Type field device and wiring open circuit or short circuit detection dip-switch selectable. When fault is detected output is de-energized until normal condition is restored.
Short output detection load resistance ≤ 50 Ω (≈ 2 mA forcing to detect fault).
Open output detection load resistance > 10 KΩ.
Fault signalling voltage free NE SPST optocoupled open-collector transistor (output de-energized in fault condition and when input power not present).
Open-collector rating 100 mA at 35 Vdc (≤ 1.5 V voltage drop).
Leakage current ≤ 50 µA at 35 Vdc.
Loop input consumption ≤ 10 mA when fault detected.
Response time ≤ 5 ms.

Isolation

Test Voltage I.S. Out/In 1.5 KV; I.S. Out/Override 1.5 KV; I.S. Out/Fault 1.5 KV; In/Fault 500 V; In/Override 500 V; Fault/Override 500 V.

Environmental conditions

Operating temperature limits -20 to + 60 °C, relative humidity max 95 % non condensing
Storage temperature limits -45 to + 80 °C.

Safety description

Safety parameters Uo/Voc = 24.8 V, Io/Isc = 147 mA, Po/Po = 907 mW at terminals 13-16 Out A. Uo/Voc = 24.8 V, Io/Isc = 108 mA, Po/Po = 667 mW at terminals 14-16 Out B. Uo/Voc = 24.8 V, Io/Isc = 93 mA, Po/Po = 571 mW at terminals 15-16 Out C. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C.

Mounting

Type EN/IEC60715 TH 35 DIN-Rail
Weight about 135 g
Connection by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2.
Location Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
Protection class IP 20.
Dimensions Width 22.5 mm, Depth 99 mm, Height 114.5 mm.

Data Sheet


Datasheet of D1048 ( EN )
D1000 Series Common Specifications and Dimensional Drawing ( EN )

Instruction Manual


Instruction Manual D1048 ( EN )
Instruction Manual D1000 Series ( EN | RU )
Ex safety instruction manual for D1000 series ( EN | IT )
INMETRO safety instruction manual for D1000 series ( PT )

Certifications


Type Description Area Number Issued by Issue Date
ATEX DEKRA ATEX D1000 Series English Certificate ( EN ) Europe DMT 01 ATEX E 042 X DEKRA 2022-04-25
EMC D1000 EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.НХ37.В.06311/20 EUROCERT 2020-08-13
Ex EAC Ex Certificate for D1000 Series ( RU ) Eurasian Community ЕАЭС RU С-IT.НА67.В.00113/20 TECHNOPROGRESS 2020-09-04
Ex FM No.3024643-3029921C Certificate ( EN ) North America 3024643-3029921C FM 2005-12-16
Ex INMETRO Certificate DNV 13.0108 X for D1000 series ( EN ) Brazil DNV 13.0108 X DNV 2022-12-10
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
IECEx DEKRA IECEx for D1000 Series ( EN ) International IECEx BVS 07.0027X DEKRA 2022-05-30
Maritime KR Maritime Certificate D1000 Series ( EN ) International MIL20769-EL001 KR 2022-07-04
SIL TUV C-IS-236198-04 SIL Certificate Summary ( EN ) International C-IS-236198-04 TUV_SUD 2022-10-14

Declarations of Conformity


EU Declaration of Conformity for D1048, D1049, D1061-077 ( EN | IT )
EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
Declaration of G3 compliance for D1000_PSD1000-PSD1001-PSD1001C-PSD1004-PSD1220-PSD1220-098 SERIES ( EN )

Dimensions


Image of D1048S_size

Connections


Drawings


2d_drawing_D1000_dwg ( EN )
3d_drawing_D1000_dwg ( EN )
3d_drawing_D1000_stp ( EN )