The single channel DIN-Rail Frequency-Pulse Converter, Repeater and Trip Amplifiers D1060S converts and repeats a low level frequency signal from magnetic pick-up, contact, proximity, open-collector transistor sensor, TTL CMOS located in Hazardous Area, into a 0/4-20 mA or 0/1-5 V or 0/2-10 V signal to drive a Safe Area load. Repeater output can be direct, divided by 10, 100, 1000, 10000, 100000, 1000000 or programmed with alarm function. One independent Alarm Trip Amplifier is also provided. Alarm energizes, or de-energizes, an SPST optocoupled open-collector transistor for high, low or low-startup alarm functions. The alarm trip point is settable over the entire input signal range. When repeater output is used as alarm output the unit provides two independent alarms.

FEATURES

  • Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
  • Magnetic pick-up, proximity input sensor.
  • Frequency range DC to 50 KHz input.
  • Repeater output direct or divided by 10, 100, 1000, 10000, 10000 or 1000000.
  • 0/4-20 mA, 0/1-5 V, 0/2-10 V Output Signal linear or reverse.
  • High Accuracy, µP controlled converter.
  • Three port isolation, Input/Output/Supply.
  • EMC Compatibility to EN61000-6-2, EN61000-6-4.
  • Fully programmable operating parameters.
  • High Density, 1 channel converter, repeater and trip amplifier per unit.
  • 250 Vrms (Um) max. voltage allowed to the Instruments associated with the barrier.

STATUS

 
   SPARE-ONLY
Next: OBSOLETE (2025-12-31)

Product lifecycle policy (EN)

CHANNELS

1

Request a free and personalized quotation!

Technical Data


Supply

Voltage 12-24 Vdc nom (10 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp.
Current Consumption 60 mA with 20 mA output and transistors energized.
Power Dissipation 1.3 W with 24 V supply, 20 mA output and transistors energized.
Max. power consumption at 30 V supply voltage, overload condition, transistors output energized and PPC1090 connected, 1.9 W.

Input

Type magnetic pick-up, contact, proximity to EN60947-5-6, open-collector transistor for frequency signal up to 50 KHz, TTL CMOS.
Magnetic pick-up sensitivity ≥ 20 mVpp up to 100 Hz input, ≥ 50 mVpp up to 1 KHz, ≥ 100 mVpp up to 5 KHz, ≥ 500 mVpp up to 20 KHz, ≥ 1 Vpp up to 50 KHz.
Switching current levels ON ≥ 2.1 mA, OFF ≤ 1.2 mA, switch current ≈ 1.65 mA ± 0.2 mA hysteresis (for proximity or transistor input).
Equivalent source 8 V 1 KΩ typical (8 V no load, 8 mA short circuit).
Integration time 100 ms
Resolution/Visualization 1 mHz for 50 Hz range, 10 mHz for 500 Hz range, 100 mHz for 5 KHz range, 1 Hz for 50 KHz range.
Input range 0 to 50.5 KHz maximum.

Burnout

Type downscale analog output signal for loss of input signal.

Output

Type 0/4 to 20 mA, on max. 600 Ω load source mode, current limited at 22 mA or 0/1 to 5 V or 0/2 to 10 V signal, limited at 11 V.
Resolution 1 µA current output or 1 mV voltage output.
Transfer characteristic linear direct or reverse.
Response time ≤ 50 ms (10 to 90 % step change).
Output ripple ≤ 20 mVrms on 250 Ω load.

Repeater Output

Type voltage free SPST optocoupled open-collector transistor.
Output factor direct 1:1 or divided by 10, 100, 1000, 10000, 100000 or 1000000.
Open-collector rating 100 mA at 35 Vdc (≤ 1.5 V voltage drop).
Leakage current ≤ 50 µA at 35 Vdc
Frequency response 50 KHz maximum

Alarm

Trip point range within rated limits of input range (see input for step resolution).
Delay time 0 to 1000 s, 100 ms step.
Hysteresis 0 to 5 Hz for 50 Hz range, 0 to 50 Hz for 500 Hz range, 0 to 500 Hz for 5 KHz range, 0 to 5 KHz for 50 KHz range (see input visualization parameters for step resolution).
Output voltage free SPST optocoupled open-collector transistor.
Open-collector rating 100 mA at 35 Vdc (≤ 1.5 V voltage drop).
Leakage current ≤ 50 µA at 35 Vdc.

Input performance

Type Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
Calibration and linearity accuracy ≤ ± 0.05 % of full scale of selected input range.
Temperature influence ≤ ± 0.005 % of full scale input range for a 1 °C change.

Output performance

Type Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
Calibration accuracy ≤ ± 0.1 % of full scale
Linearity error ≤ ± 0.05 % of full scale.
Supply voltage influence ≤ ± 0.05 % of full scale for a min to max supply change.
Load influence ≤ ± 0.05 % of full scale for a 0 to 100 % load resistance change.
Temperature influence ≤ ± 0.01 % on zero and span for a 1 °C change.

Isolation

Test Voltage I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; Analog Out/Supply 500 V; Analog Out/Digitals Out 500 V; Digital Outs/Supply 500 V; Digital Out/Digitals Out 500 V;

Environmental conditions

Operating temperature limits –20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C.
Storage temperature limits – 45 to + 80 °C.

Safety description

Safety parameters Uo/Voc = 10.9 V, Io/Isc = 1.1 mA, Po/Po = 3 mW at terminals 13-16. Uo/Voc = 15.5 V, Io/Isc = 13 mA, Po/Po = 48 mW at terminals 14-15. Uo/Voc = 10.9 V, Io/Isc = 23 mA, Po/Po = 60 mW at terminals 15-16. Ui/Vmax = 30 V, Ci = 0 nF, Li = 0 nH at terminals 13-16. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60°C.

Mounting

Type EN/IEC60715 TH 35 DIN-Rail.
Weight about 155 g.
Connection by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2.
Location Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
Protection class IP 20.
Dimensions Width 22.5 mm, Depth 99 mm, Height 114.5 mm.

Data Sheet


Datasheet of D1060 ( EN )
D1000 Series Common Specifications and Dimensional Drawing ( EN )

Instruction Manual


Instruction Manual D1060 ( EN )
Instruction Manual D1000 Series ( EN | RU )
Ex safety instruction manual for D1000 series ( EN | IT )
CCC Ex safety instruction manual for D1000 series ( EN | CN )
INMETRO safety instruction manual for D1000 series ( PT )
UL Control Drawing D1060 ( EN )

Certifications


Type Description Area Number Issued by Issue Date
ATEX DEKRA ATEX D1000 Series English Certificate ( EN ) Europe DMT 01 ATEX E 042 X DEKRA 2022-04-25
ATEX IMQ Zone 2 Applications D1000 Series Certificate ( EN ) Europe IMQ 09 ATEX 013 X IMQ 2022-05-03
EMC D1000 EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.НХ37.В.06311/20 EUROCERT 2020-08-13
Ex D1000 CCC certificate for China ( EN ) China 2023322316005683 NEPSI 2023-12-01
Ex CML D1012, D1014, D1045, D1060, D1080, D1081, D1180 certificate for Japan ( EN ) Japan CML 20JPN2316X CML 2024-03-11
Ex EAC Ex Certificate for D1000 Series ( RU ) Eurasian Community ЕАЭС RU С-IT.НА67.В.00113/20 TECHNOPROGRESS 2020-09-04
Ex UL-cUL D1060 Divisions and Zones ( EN ) North America 20130115-E222308F UL 2013-01-15
Ex FM No.3024643-3029921C Certificate ( EN ) North America 3024643-3029921C FM 2005-12-16
Ex INMETRO Certificate DNV 13.0108 X for D1000 series ( EN ) Brazil DNV 13.0108 X DNV 2022-12-10
IECEx IMQ IECEx Zone 2 Applications D1000 Series Certificate ( EN ) International IECEx IMQ 13.0011X IMQ 2022-05-03
IECEx DEKRA IECEx for D1000 Series ( EN ) International IECEx BVS 07.0027X DEKRA 2022-05-30
Maritime KR Maritime Certificate D1000 Series ( EN ) International MIL20769-EL001 KR 2022-07-04
Metrological Metrological Certificate Russia for D1000 Series ( RU ) Russia 64283-11 ROSSTANDART 2021-03-10

Declarations of Conformity


EU Declaration of Conformity D1000 series ( EN | IT )
EU Declaration of Conformity for D1000 series (zone 2) ( EN | IT )
EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
Declaration of G3 compliance for D1000_PSD1000-PSD1001-PSD1001C-PSD1004-PSD1220-PSD1220-098 SERIES ( EN )