D5016SK G.M. International s.r.l.
GM International

D5016SK
I.S. SIL3 2-Wire Active HART® Tx Current Repeater

The Current Repeater D5016 module is a high integrity analog input interface suitable for applications requiring SIL 3 level in safety related systems for high risk industries. It repeats a 2-wire active 4- 20 mA current signal input in floating circuit to drive a Safe Area load. The module allows bi-directional communication signals, for HART® devices.

FEATURES

  • SIL 3 / SC 3
  • Input from Zone 0/Div. 1
  • Installation in Zone 2/Div. 2
  • 2 fully independent channels
  • 4-20 mA Source-Sink Output
  • HART® compatible
  • High Accuracy
  • Three port isolation, Input/Output/Supply
  • High Density, two channels per unit

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

1

Request a free and personalized quotation!

Technical Data


Supply

Voltage 24 Vdc nom (18 to 30 Vdc), reverse polarity protected
Current Consumption 20 mA @ 24 Vdc with 20 mA out, typical.
Power Dissipation 1.00 W @ 24 Vdc with 20 mA output on 250 Ω load and 24 Vdc output supply for sink models, typical.

Input

Type 4 to 20 mA (separately powered input, voltage drop ≤ 7 V), reading range 0 to 22 mA.
HART Impedance 225 Ω, typical.

Output

Type 4 to 20 mA.
Sink out voltage range 2 to 30 V.
Load range 0 to 500 Ω, with conventional Tx input 250 Ω nom (160 to 500 Ω), with smart Tx input.
Current limitation 24 mA (up to 450 Ω load) ≤ max current ≤ 26 mA.
Response time 20 ms (10 to 90 % step change).

Performance

Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
Calibration accuracy ≤ ± 20 μA.
Linearity accuracy ≤ ± 20 μA.
Temp. influence ≤ ± 2 μA/°C.

Isolation

Test Voltage I.S. In/Out 2.5 kV; I.S. In/Supply 2.5 kV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Storage temperature temperature limits –45 to +80 °C.

Safety description

Equipment Associated apparatus and non-sparking electrical equipment.
Safety parameters Uo = 8.8 V, Io = 0 mA, Po = 0 mW at terminals 7-8, 9-10 Ui = 30 V, Ii = 100 mA, Ci = 1.1 nF, Li = 0 nH at terminals 7-8, 9-10

Mounting

Type DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board.
Weight about 115 g.
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
Dimensions Width 12.5 mm, Depth 123 mm, Height 120 mm.

Data Sheet


Datasheet of D5016 ( EN )
D5000 Series Common Specifications and Dimensional Drawing ( EN )

Instruction Manual


Safety Manual D5016 ( EN )
ATEX safety instruction manual for D5000 series ( EN | IT )
CCC Ex safety instruction manual for D5000 series ( EN | CN )
UL Control Drawing D5016 ( EN )

Certifications


Type Description Area Number Issued by Issue Date
ATEX UL ATEX D5016 Series English Certificate ( EN ) Europe UL 22 ATEX 2892X UL 2022-12-19
Ex D5000 CCC certificate for China ( EN ) China 2020322316000978 NEPSI 2024-03-22
Ex UL-cUL D5016 Divisions and Zones ( EN ) North America E222308-20221220 UL 2022-12-28
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
IECEx UL IECEx D5016 Series English Certificate ( EN ) International IECEx ULD 22.0034X UL 2022-12-19
SIL TUV IT 22 SIL 0001 A SIL Certificate Summary ( EN ) International TUV IT A 22 SIL 0001 Rev.2 TUV_SUD 2023-06-15

Declarations of Conformity


EU Declaration of Conformity of D5016 ( EN | IT )
EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
Declaration of Conformity G3 compliance ( EN )

Dimensions


Image of D5016_size

Connections


RELATED PRODUCTS