TB-D5016-INV-006 G.M. International s.r.l.
GM International

TB-D5016-INV-006
16-pos Term. Board for Foxboro FBM200 DI cards

This Termination Board (TB) provides direct connection between the I/O Card of the system and D5000 / D6000 Series modules. The Intrinsically Safe protection and signal isolation between Safe and Hazardous Area are provided by D5000 Series Associated Apparatus. The 24 Vdc Power Supply of the TB is connected to two plug-in terminal blocks, for a redundant power supply.

FEATURES

  • Foxboro FBM200 DI Cards board interfaces
  • 16 positions Termination Board for up to 32 channels
  • Lower cables installation and maintenance costs
  • Power supplies fault monitoring
  • Mounting hardware provided for single DIN Rail or wall

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

32

Request a free and personalized quotation!

Technical Data


General

Number of positions 16
Maximum number of channels 32

Supply

Voltage 24 Vdc nom (20 to 30 Vdc), reverse polarity protected, double terminal blocks for redundant power supply, with OR diodes to mix supply voltages.
Max allowed current consumption 1.5 A (as total supply).
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm².
Protection fuse 4 A time lag.

Fault detection

Type The on-board diagnostic monitors both power supplies integrity and the module cumulative fault. Any malfunction is reported by deactivating a relay and activating the corresponding LEDs. Alarm is issued if: 1) Power supply 1 or 2 < 18 Vdc or 2) Power supply 1 or 2 > 32 Vdc or 3) Module cumulative fault ON. Alarm is removed if: 1) 20 Vdc < Power supply 1 and 2 < 30 Vdc and 2) No module cumulative fault.
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm².
Output rating 2 A 36 Vac 72 VA, 2 A 48 Vdc 80 W (resistive load).

I/O Card Interface

Connection 1 x SUBD, 37-poles male connector (require female mating connector).
Cable system cable Type 4.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Max altitude 2000 m a.s.l.
Storage temperature temperature limits –45 to +80 °C.

Mounting

Type Hardware included for mounting on single DIN-rail 35 mm or on wall (thread or self tapping screws provided).
Weight about 400 g, excluding modules and mounting kit.
Location installation in Safe Area.
Dimensions Width 267 mm, Depth 176 mm, Height 125 mm.

Data Sheet


Datasheet of TB-D5016-INV-006 ( EN )
Schneider Foxboro TB Summary ( EN | FR | JA | CN | PT | IT | ES | DE )

Certifications


Type Description Area Number Issued by Issue Date
EMC 5700 and TB EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.АЖ38.В.00125/19 EUROCERT 2019-05-30

Declarations of Conformity


EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
EU Declaration Termination Boards TB, TBE, TUE ( EN )
Declaration of Conformity G3 compliance ( EN )

Dimensions


Image of TB-D5016-INV-006_size

Connections