D6072D G.M. International s.r.l.
GM International

D6072D
SIL2 Multifunction Temperature Converter

The Multifunction Temperature Converter D6072 accepts a low level dc signal from millivolt, thermocouple or 2-3-4 wire resistance/RTD or transmitting potentiometer sensor and converts, with isolation, the signal to drive a load, suitable for applications requiring SIL 2 level in safety related systems for high risk industries. Output signal can be direct or reverse. Modbus RTU RS-485 output is available on Bus connector. Cold junction compensation can be programmed as Internal: provided by an internal temperature sensor; Fixed: to a user-customizable temperature value; Remote: (only D6072D) connecting compensation RTD to one of the two ch. For D6072D module: duplicator function provides two independent outputs from one single input. Output function can be configured as: Adder, subtractor, low/high selector. Modules are provided with alarm function, which is available via photoMOS output.

FEATURES

  • SIL 2 / SC 3
  • Installation in Zone 2
  • Installation in Div. 2
  • mV, TC, 2/3/4wire res./RTD or potentiometer input
  • Duplication/inversion/scaling/custom output
  • Selectable CJC: internal PT1000, external RTD or fixed
  • Fastest integration time: 50 ms
  • Burnout/internal/cjc/in sensor fault monitor
  • Alarm output with user-settable trip points
  • Modbus RTU RS-485 for monitor & configuration
  • Fully programmable operating parameters
  • High Accuracy, µP controlled A/D converter
  • Three port isolation, Input/Output/Supply
  • High Density, two channels per unit

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

2

Request a free and personalized quotation!

Technical Data


Supply

Voltage 24 Vdc nom (18 to 30 Vdc), reverse polarity protected
Current Consumption 50 mA @ 24 Vdc with 20 mA out, typical.
Power Dissipation 1.0 W @ 24 Vdc with 20 mA out, typical.

Input

Type Millivolt, thermocouple, 2-3-4 wire RTD or 3 wire transmitting potentiometer. Refer to Instruction Manual for more details.
Integration time from 50 ms to 500 ms.
Input range ±500 mV (TC/mV), 0-4 kΩ (RTD/res), up to 10 kΩ (pot).
Thermocouple reference junction compensation programmable: internal Pt1000, fixed, external, or remote.

Output

Type Fully customizable 0/4 to 20 mA, on max. 300 Ω load source mode, current limited @ 24 mA. Refer to Instruction Manual for more details.
Transfer characteristic linear, direct or reverse on all input sensors.
Response time ≤ 20 ms (10 to 90 % step).

Modbus interface

Type Modbus RTU RS-485 up to 115.2 kbps for monitor/configuration/control.

Input performance

Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature, slow integration mode, 3/4 wires configuration for RTD.
Calibration and linearity accuracy refer to Instruction Manual.
Temp. influence refer to Instruction Manual.
Ref. junction compensation accuracy ≤ ± 1 °C.

Output performance

Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature, slow integration mode, 3/4 wires configuration for RTD.
Calibration accuracy ≤ ± 10 µA.
Linearity error ≤ ± 10 µA.
Temp. influence ≤ ± 2 µA/°C

Isolation

Test Voltage In/Out 2.5 kV; In/Supply 2.5 kV; In/In 500 V; Out/Supply 500 V; Out/Out 500 V.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Storage temperature temperature limits –45 to +80 °C.

Mounting

Type DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board.
Weight about 135 g
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
Dimensions Width 12.5 mm, Depth 123 mm, Height 120 mm.

Data Sheet


Datasheet of D6072 ( EN | FR | JA | IT | ES | DE | RU | CN | PT )

Instruction Manual


Instruction Manual D6072 ( EN )
Instruction Manual D5000-D5200 Series ( EN )
Safety Manual D6072, D6072-099 ( EN )
Ex safety instruction manual for D6000 series ( EN | IT )
Ex safety instruction manual for D6000 series ( RU )

Certifications


Type Description Area Number Issued by Issue Date
ATEX DEKRA ATEX D6072 Series English Certificate ( EN ) Europe BVS 20 ATEX E 059 X DEKRA 2020-09-24
EMC D5000/D6000 EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.АЖ38.В.00126/19 EUROCERT 2019-05-31
Ex EAC Ex Certificate for D6000 and TB/TBE Series ( RU ) Eurasian Community ЕАЭС RU С-IT.AA87.В.00796/21 CCVE 2021-09-20
Ex UL-cUL D6072, D6072-087, D6072-096, D6072-099 Divisions ( EN ) North America E222308-20190531 UL 2022-05-12
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
IECEx DEKRA IECEx D6072 Series English Certificate ( EN ) International IECEx BVS 20.0047X DEKRA 2020-10-08
Metrological Metrological Certificate Belarus for D5000/D6000 Series ( BE ) Belarus 15507 ROSSTANDART 2022-08-30
Metrological Metrological Certificate Kazakhstan for D5000/D6000 series ( KK ) Kazakhstan 1152 KMC 2021-08-05
Metrological Metrological Certificate Russia for D5000/D6000 series ( RU ) Russia OC.C.32.004.A n. 77881 ROSSTANDART 2020-07-28
SIL TUV C-IS-722160171 SIL Certificate Summary ( EN ) International C-IS-722160171 TUV_SUD 2022-10-14

Declarations of Conformity


EU Declaration of Conformity of D6072 ( EN | IT )
EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
Declaration of Conformity G3 compliance ( EN )

Dimensions


Image of D6072_size

Connections


Software


SWC5090 - Configurator for D5000/D5200, D6000/D6200 Series isolators ( EN )