TBE-D5001-HRT-003 G.M. International s.r.l.
GM International

TBE-D5001-HRT-003

TBE-D5001-HRT-003
SIL3 HART® Mux Term. Board for GMI Term. Board Connection

This Termination Board with Enclosure (TBE) allows the remote monitoring of any HART®-compatible 4/20 mA field loop. This is obtained by one locally mounted HART® Multiplexer Modem 5700 series and by interface connectors to access field smart devices. The single TBE-D5001-HRT-003 Termination Board supports 64 channels. Yet, it could be extended with additional units (up to 4) to manage all 256 channels available on the HART® Multiplexer Modem 5700 series. The Mux unit connects, via the RS-485 interface, to an external PC running an FDT-based software package (PACTware™, etc...) through a dedicated Device Type Manager (DTM). The PC can communicate with multiple Mux units, located on different boards, in a multi-drop RS-485 mode. The HART® Termination Board TBE-D5001-HRT-003 is SIL 3 certified as non-interfering with the signal loops. The 24 Vdc Power Supply of the TBE is connected to two plug-in terminal blocks, for a redundant power supply.

FEATURES

  • SIL 3 / SC 3
  • Installation in Zone 2/Div. 2
  • HART® Multiplexing Board of up to 64 analog signals (extendable to 256)
  • 4/20 mA loops isolated with dual capacitors (short circuit proof)
  • Dedicated terminal to connect RS-485 cable shield
  • Double terminal to ease RS-485 cable multi-drop
  • Lower cables installation and maintenance costs
  • Redundant power supply
  • Mounting hardware provided for single DIN Rail mounting kit

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

64

Request a free and personalized quotation!

Technical Data


General

Number of positions 1 x HART® Multiplexer Modem 5700 series.
Maximum number of channels 64 on a single board, extendable to 256 with 4 boards and 1 HART® Multiplexer Modem 5700 series. Up to 16128 smart devices in full topology with 252 boards and 63 HART® Multiplexer Modem 5700 series.

Supply

Voltage 24 Vdc nom (20 to 30 Vdc), reverse polarity protected, double terminal blocks for redundant power supply, with OR diodes to mix supply voltages.
Current Consumption 35 mA @ 24 Vdc with full topology (4 boards), typical.
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm².
Protection fuse 2 A time lag.

HART Interface

Connection 4 x 34-poles receptacle connector (require female mating connector).
Cable flat cable CABF032.
Channel-to-channel isolation voltage 50 V.

Additional TBs interface

Connection 2 x flat cable 10 poles male connectors (requires female mating connector).
Cable flat cables CABF022, CABF023, CABF024.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Max altitude 2000 m a.s.l.
Storage temperature temperature limits –45 to +80 °C.

Mounting

Type Hardware included for mounting on single DIN-rail 35 mm.
Weight about 710 g (+ 50 g plastic clips or 380 g metal clips).
Location installation in Safe Area or Zone 2, Group IIC T4, or Class 1, Div. 2, Group A, B, C, D, T4.
Dimensions Width 235 mm, Depth 135 mm, Height 154 mm.

Data Sheet


Datasheet of TBE-D5001-HRT-003 ( EN )

Instruction Manual


Instruction Manual Termination Boards HART ( EN )
Instruction Manual for installation of TBE-FIX-MT-xxx (valid for TBE-HRT & TBE-TRI & TBE-GMI) ( EN )
Instruction Manual for installation of TBE-FIX-PL-001 (valid for TBE-HRT & TBE-TRI & TBE-GMI) ( EN )
Safety Manual 5700 or 5700-110 + TBE-D5001-HRT-003, -004, -005, -006, -007 or TBE-D5001-TRI-001 ( EN )
Ex safety instruction manual for TB, TBE series ( EN | IT )

Certifications


Type Description Area Number Issued by Issue Date
ATEX UL ATEX 5700, TBE-D5001-HRT-003, TBE-D5001-HRT-xxx series English Certificate ( EN ) Europe UL 20 ATEX 2492X UL 2021-02-25
EMC 5700 and TB EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.АЖ38.В.00125/19 EUROCERT 2019-05-30
Ex UL-cUL TBE-D5001-HRT-003, TBE-D5001-HRT-xxx series Divisions ( EN ) North America E222308-20210226 UL 2021-03-18
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
IECEx UL IECEx 5700, TBE-D5001-HRT-003, TBE-D5001-HRT-xxx series English Certificate ( EN ) International IECEx ULD 20.0042X UL 2021-02-25
SIL TUV C-IS-272994-01 SIL Certificate Summary ( EN ) International C-IS-272994-01 TUV_SUD 2022-10-14

Declarations of Conformity


EU Declaration of Conformity for 5700, TBE-D5001-HRT-xxx ( EN | IT )
EU Declaration Termination Boards TB, TBE, TUE ( EN )
Declaration of Conformity G3 compliance ( EN )

Dimensions


Image of TBE-D5001-HRT-003_size

Connections