TB-D5001-HRT-004

SIL 3 HART® Multiplexer Termination Board 1 position for up to 32 channels (extendable to 256 channels)

Description

The HART® Termination Board model TB-D5001-HRT-004 allows the remote monitoring of any HART®-compatible 4/20 mA field loop. It is suitable for interfacing AI cards of safety PLCs with typical input impedance of 250 Ω and AO cards. This is obtained by one locally mounted HART® Multiplexer Modem 5700 and by terminal block interface connectors to access the relevant loops. The board is installed in series to the loops and is totally transparent to both transmitter and receiver. The single TB-D5001-HRT-004 Termination Board supports 32 channels. Yet, it can be extended with additional TB-D5001-HRT-004 units (up to 8) to manage all 256 channels available on the HART® Multiplexer Modem 5700. The Mux unit connects, via the RS-485 interface, to an external PC running an FDT based software package (PACTware™, etc...) through a dedicated Device Type Manager (DTM). The PC can communicate with multiple Mux units, located on different boards, in a multi-drop RS-485 mode. The HART® Termination Board TB-D5001-HRT-004 is SIL 3 certified as non-interfering with the signal loops.

Features

• SIL 3 according to IEC 61508:2010 Ed. 2
• Systematic capability SIL 3
• Transparent Board for HART® Multiplexing of up to 32 analog signals (extendable to 256 channels with 7 additional TB-D5001-HRT-004 units)
• Suitable for interfacing AI cards of safety PLCs with typical input impedance of 250 Ω and AO cards
• Redundant Power Supply connection by screw terminals
• Supply is fuse protected and with LED indication
• RS-485 interface terminals to communicate with the HART® Mux unit
• HART® loop interface terminal block connectors
• HART® channels isolated with dual capacitors (short circuit proof)
• Spare fuse provided
• Includes hardware for Easy installation in three modes:
- Wall mounting, M4 Threads
- Wall mounting, Self-Threading
- Din Rail mounting
Image of TB-D5001-HRT-004 (Web)

Download

    Datasheet of TB-D5001-HRT-004 ( EN )
    Instruction Manual HART Mux modem 5700 ( EN )
    Safety Manual 5700-xxx + TB-D5001-HRT-003, -004, -005, -006, -007 ( EN )
    EAC_EMC > EAC > 5700 and TB EAC EMC Declaration of Conformity ( RU )
    QMS_FS > TUV_SUD > TUV IT 22 SIL 0093 Functional Safety Certificate ( EN )
    SIL > TUV_SUD > TUV C-IS-272994-01 SIL Certificate Summary ( EN )
    EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
    EU Declaration Termination Boards TB, TBE, TUE ( EN )
    Declaration of Conformity G3 compliance ( EN )

Status

PHASE-OUT
Next: SPARE-ONLY (01/01/2029)

> Product lifecycle policy ( EN )

Alternatives

TBE-D5001-HRT-004

 