D6072S-096 G.M. International s.r.l.
GM International

D6072S-096
SIL2 Thermocouple/mV Repeater

The Thermocouple/mV Repeater D6072-096 accepts a low level dc signal from millivolt or thermocouple sensor and repeats, with isolation, the signal, suitable for applications requiring SIL 2 level in safety related systems for high risk industries. For D6072D-096 module: duplicator function provides two independent outputs from one single input.

FEATURES

  • SIL 2 / SC 3
  • Installation in Zone 2
  • Installation in Div. 2
  • mV or thermocouple input
  • Output duplication
  • Fully programmable operating parameters
  • High Accuracy, µP controlled A/D converter
  • Three port isolation, Input/Output/Supply
  • High Density, two channels per unit

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

1

Request a free and personalized quotation!

Technical Data


Supply

Voltage 24 Vdc nom (18 to 30 Vdc), reverse polarity protected
Current Consumption 30 mA @ 24 Vdc, typical.
Power Dissipation 0.6 W @ 24 Vdc, typical.

Input

Type Millivolt or any type of thermocouple within Input Range.
Integration time 75 ms (fast), 375 ms (slow), user selectable.
Input range -10 to +100 mV.
Thermocouple burnout current ≤ 50 µA.

Output

Type Millivolt.
Transfer characteristic linear.
Response time ≤ 20 ms (10 to 90 % step).
Output range -10 to +100 mV.

Fault

Type Output reflects burnout/internal fault condition via highscale (+110 mV) value forcing. Fault condition is also signaled via BUS and red LED on front panel.

Input performance

Ref. Conditions 24 V supply, 23 ± 1 °C ambient temperature, slow integration mode.
Calibration and linearity accuracy ≤ ± 10 µV.
Temp. influence ≤ ± 3 µV/°C, typical.

Output performance

Ref. Conditions 24 V supply, 23 ± 1 °C ambient temperature, slow integration mode.
Calibration and linearity accuracy ≤ ± 10 µA.
Temp. influence ≤ ± 3 µV/°C, typical.

Isolation

Test Voltage In/Out 2.5 kV; In/Supply 2.5 kV; In/In 500 V; Out/Supply 500 V; Out/Out 500 V.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Storage temperature temperature limits –45 to +80 °C.

Mounting

Type DIN-Rail 35 mm, with or without Power Bus.
Weight about 130 g
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
Dimensions Width 12.5 mm, Depth 123 mm, Height 120 mm.

Data Sheet


Datasheet of D6072-096 ( EN | IT | ES | FR | DE | RU | JA | CN | PT )

Instruction Manual


Instruction Manual D6072-096 ( EN )
Instruction Manual D5000-D5200 Series ( EN )
Safety Manual D6072-096 ( EN )
Ex safety instruction manual for D6000 series ( EN | IT )
Ex safety instruction manual for D6000 series ( RU )

Certifications


Type Description Area Number Issued by Issue Date
ATEX DEKRA ATEX D6072 Series English Certificate ( EN ) Europe BVS 20 ATEX E 059 X DEKRA 2020-09-24
EMC D5000/D6000 EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.PA08.B.82326/24 CONTROL 2024-09-26
Ex EAC Ex Certificate for D6000 and TB/TBE Series ( RU ) Eurasian Community ЕАЭС RU С-IT.AA87.В.00796/21 CCVE 2021-09-20
Ex UL-cUL D6072, D6072-087, D6072-096, D6072-099 Divisions ( EN ) North America E222308-20190531 UL 2022-05-12
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
IECEx DEKRA IECEx D6072 Series English Certificate ( EN ) International IECEx BVS 20.0047X DEKRA 2020-10-08
Metrological Metrological Certificate Kazakhstan for D5000/D6000 series ( KK ) Kazakhstan 1152 KMC 2021-08-05
Metrological Metrological Certificate Russia for D5000/D6000 series ( RU ) Russia OC.C.32.004.A n. 77881 ROSSTANDART 2020-07-28
SIL TUV C-IS-722160171 SIL Certificate Summary ( EN ) International C-IS-722160171 TUV_SUD 2022-10-14

Declarations of Conformity


EU Declaration of Conformity of D6072 ( EN | IT )
EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
Declaration of Conformity G3 compliance ( EN )

Dimensions


Image of D5072_096_size

Connections


Software


SWC5090 - Configurator for D5000/D5200, D6000/D6200 Series isolators ( EN )
Instruction Manual SWC5090 ( EN )

RELATED PRODUCTS


ACCESSORIES