5700

HART® Multiplexer Modem 256 channels

Description

The HART® Multiplexer Modem 5700 interfaces up to 256 smart devices (transmitters, I/P, proportional valves, etc…) in a HART® Network. Each device can be fully identified, configured and monitored by a remote PC running an FDT-based software package (PACTware™, etc...) through a dedicated Device Type Manager (DTM). The module is intended to be mounted on the following Termination Boards:


• TB-D5001-HRT-003: to be used with G.M. International AI/AO Termination Boards;
• TB-D5001-HRT-004: to be used with DIN-Rail mounted barriers/isolators or direct field connections, for 4-20mA loop signal;
• TB-D5001-HRT-005: to be used with DIN-Rail mounted barriers/isolators or direct field connections, for 1-5V loop signal.



Termination board types can be combined to manage different interfaces at the same time, simply respecting maximum number of connected channels. The HART® Multiplexer Modem 5700 is SIL 3.
In order to communicate with the hardware, an RS232/RS485 converter should be connected to the serial port of the Host. The suggested converter is the D1061S.

The minimum required software tools, to be able to operate the HART® network, are the following:

Features

• SIL 3 / SC 3
• Input from Zone 2, installation in Zone 2.
• Up to 256 channels (extendable to 16128 with 63 multi-drop units).
• HART® RS-485 interface to access field smart devices.
• Three port isolation, Field Interface/Serial Interface/Supply.
• Simplified installation on custom Termination Boards.
Image of FL3_7073_scontorno.png (WEB)

Download

    D5000 Series Common Specifications and Dimensional Drawing ( EN )
    Datasheet of Hart Mux 5700 ( EN )
    Ex safety instruction manual for D5000 series ( EN | IT )
    Instruction Manual HART Mux modem 5700 ( EN )
    Safety Manual 5700-xxx + TB-D5001-HRT-003, -004, -005, -006, -007 ( EN )
    HART Mux 5700 Device Management Software compatibility ( EN )
    ATEX > UL > UL ATEX 5700, TBE-D5001-HRT-003, TBE-D5001-HRT-xxx series English Certificate ( EN )
    EAC_EMC > EAC > 5700 and TB EAC EMC Declaration of Conformity ( RU )
    HAZARDOUS_LOCATION > UL > UL-cUL 5700 Divisions ( EN )
    IECEX > UL > UL IECEx 5700, TBE-D5001-HRT-003, TBE-D5001-HRT-xxx series English Certificate ( EN )
    QMS_FS > TUV_SUD > TUV C-IS-236198-09 Functional Safety Certificate ( EN )
    SIL > GMI > TUV C-IS-272994-01 SIL Certificate Summary ( EN )
    EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
    EU Declaration of Conformity for 5700, TBE-D5001-HRT-xxx ( EN | IT )
    Declaration of Conformity G3 compliance ( EN )
    2D_drawing_D5000_dwg ( EN )
    3D_drawing_D5000_dwg ( EN )
    3D_drawing_D5000_stp ( EN )
    DTM5700 - Device Type Manager for 5700 HART® Mux ( Download )
    SWC5090 - Configurator for D5000/D5200, D6000/D6200 Series isolators ( Download )
    Driver of PPC5092 ( Download )
    PPC5092D5000 Series Adapter for Configuration

Status

AVAILABLE
> Product lifecycle policy ( EN )

 

Request a quotation

« Previous: USBADAPTER
5700
Next: BUS »