Supply |
Voltage
|
115-230 Vac, 50-60 Hz nom (85 to 264 Vac, 48 to 400 Hz) or 100 to 350 Vdc,
ripple within voltage limits ≤ 10 Vpp.
Limit supply voltage to 250 Vrms for Instrinsic Safety applications.
|
Current consumption @ 115 Vac
|
30 mA with short input and relays energized.
|
Current consumption @ 230 Vac
|
20 mA with short input and relays energized.
|
Max. power consumption
|
264 Vac supply voltage, short circuit input and
relays energized, 2.2 W.
|
Input switching current levels |
Type
|
DIP switch settable at ≈ 8.0, 11.0, 14.0, 17.0 mA trip point.
Sensor supply current range is 0 to 5, 3 to 8, 6 to 11, 9 to 14 mA,
switching current ≈ 8.0 mA ± 0.5 mA hysteresis.
|
Input equivalent source
|
13.0 V 150 Ω typical
(13 V no load, 25 mA short circuit limited current).
|
Output |
Type
|
voltage free SPDT relay contact.
|
Contact material
|
AgCdO.
|
Contact rating
|
2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load).
|
DC Load breaking capacity
|
See Instruction Manual
|
Mechanical / electrical life
|
30 * 106 / 1 * 105 operation, typical.
|
Operate / release time
|
7 / 3 ms typical.
|
Bounce time NO / NC contact
|
3 / 5 ms.
|
Response time
|
20 ms.
|
Frequency response
|
10 Hz maximum.
|
Isolation |
Test Voltage
|
I.S. In/Out 2.5 KV; I.S. In/Supply 2.5 KV; I.S. In/I.S. In 500 V;
Out/Supply 2.5 KV; Out/Out 2.5 KV.
|
Storage
|
temperature limits -20 to + 60 °C,
relative humidity max 90 % non condensing, up to 35 °C.
|
Environmental conditions |
Operating
|
temperature limits -20 to + 60 °C,
relative humidity max 90 % non condensing, up to 35 °C.
|
Storage
|
temperature limits – 45 to + 80 °C.
|
Safety description |
Safety parameters
|
Uo/Voc = 15.8 V, Io/Isc = 109 mA, Po/Po = 428 mW at terminals 13-16, 9-12.
Uo/Voc = 15.8 V, Io/Isc = 13 mA, Po/Po = 51 mW at terminals 14-16, 13-15, 10-12,9-11.
Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C.
|
Weight
|
EN/IEC60715 TH 35 DIN-Rail.
|
Connection
|
about 160 g.
|
Location
|
by polarized plug-in disconnect screw terminal blocks to accomodate
terminations up to 2.5 mm2.
|
Protection class
|
Safe Area installation.
|
Dimensions
|
IP 20.
|
Mounting |
Type
|
EN/IEC60715 TH 35 DIN-Rail.
|
Weight
|
about 160 g.
|
Connection
|
by polarized plug-in disconnect screw terminal blocks to accomodate
terminations up to 2.5 mm2.
|
Location
|
Safe Area installation.
|
Protection class
|
IP 20.
|
Dimensions
|
Width 22.5 mm, Depth 99 mm, Height 114.5 mm.
|