D5096S-106 G.M. International s.r.l.
GM International

D5096S-106
SIL3 Relay Low-V Module for 5 A NE/ND Loads with LFD

The D5096-106 is a relay module suitable for switching safety related circuits, up to SIL 3 level, for high risk industries. It provides isolation between input and output contacts. It makes available 2+2 NO relay contacts connected in parallel and then in series to avoid spurious trip and to increase process availability. High process availability SIL 3 Safety Function for both Normally Energized (NE) and Normally De-energized (ND) / F&G loads is available. Load can be isolated from supply on both polarities. This model is specifically designed to reach high functional safety at input voltage. Line and load short/open circuit detection and load voltage monitoring are provided, both when the load is off and when the load is on. The fault in the field is directly mirrored to the PLC DO and it is also reported by opening the fault output.

FEATURES

  • SIL 3 / SC 3 for NE/ND loads with NE/ND driver
  • Installation in Zone 2
  • Up to 5 A functional / 6 A inrush current
  • Low input voltage
  • Load disconnection on both supply lines available
  • High process availability to avoid spurious trips
  • Compatible with DCS/PLC pulse testing
  • Line & Load short/open circuit detection
  • Load voltage monitoring
  • Field fault mirroring to the PLC DO
  • Service contact available
  • Input/Output/Supply isolation

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

1

Request a free and personalized quotation!

Technical Data


Supply

Type 24 Vdc nom (18 to 30 Vdc), reverse polarity protected.
Current Consumption 15 mA @ 24 Vdc, typical.
Power Dissipation 0.35 W @ 24 Vdc, typical.

Input

Type 24 Vdc nom (20 to 28.8 Vdc), reverse polarity protected. Relay coils are internally protected with suppressor diodes.
Current Consumption 45 mA @ 24 Vdc, typical.
Power Dissipation 1.1 W @ 24 Vdc, typical.

Output

Type Voltage free 2+2 SPST relay contact (2 paralleled contacts in series) at terminals 7-11 and 8-12, close when relay energized, open in de-energized condition.
Contact material Ag Alloy (Cd free), gold plated.
Contact rating 5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load).
Contact min. switching current 1 mA.
Contact inrush current 6 A @ 24 Vdc, 250 Vac.
DC and AC load breaking capacity refer to Instruction Manual.
Contact current derating refer to Instruction Manual.
Mechanical / electrical life: 5 * 10⁶ / 3 * 10⁴ operation, typical.
Operate / release time 30 ms / 30 ms, typical.

Fault

Type Load & line short/open circuit, supply voltage monitoring.
Line/load off ok 25 Ω ≤ resistance ≤ 19 kΩ, typical.
Line/load off fault resistance ≤ 15 Ω or ≥ 21 kΩ, typical.
Line/load on ok 15 mA rms ≤ current ≤ 5 A rms, typical.
Line/load on fault current ≤ 5 mA rms or ≥ 6 A rms, typical.
Load supply voltage ok ≥ 20 Vdc/Vac, typical.
Load supply voltage fault ≤ 5 Vdc/Vac, typical.
Fault signalling voltage free NE SPST optocoupled open-collector transistor (output de-energized in fault condition).
Fault rating 100 mA @ 35 Vdc.
Fault output voltage drop < 1 V.
Response time 0.5 s, typical.

Isolation

Test Voltage Out/In 1.5 kV; Out/Supply 1.5 kV; Out/Fault Out 1.5 kV; In/Supply 500 V; In/Fault Out 500 V; Supply/Fault Out 500 V.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Storage temperature temperature limits -45 to +80 °C.

Mounting

Type DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board.
Weight about 125 g.
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
Dimensions Width 12.5 mm, Depth 123 mm, Height 120 mm.

Data Sheet


Datasheet of D5096-106 ( EN | DE | ES | FR | IT | JA | RU | CN | PT )
D5000 Series Common Specifications and Dimensional Drawing ( EN )

Instruction Manual


Instruction Manual D5096-106 ( EN )
EAC safety instruction manual for D5000 series ( EN | RU )
Instruction Manual D5000-D5200 Series ( EN )
ATEX safety instruction manual for D5000 series ( EN | IT )
Safety Manual D5096S-106 ( EN )
CCC Ex safety instruction manual for D5000 series ( EN | CN )
Ex safety instruction manual for D5000 series ( RU )
INMETRO safety instruction manual for D5000 series ( PT )

Certifications


Type Description Area Number Issued by Issue Date
ATEX DEKRA ATEX D5000 Relay Series English Certificate ( EN ) Europe BVS 10 ATEX E 114 X DEKRA 2022-04-12
EMC D5000/D6000 EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.PA08.B.82326/24 CONTROL 2024-09-26
Ex D5000 CCC certificate for China ( EN ) China 2020322316000978 NEPSI 2024-03-22
Ex EAC Ex Certificate for D5000 Series (2nd half) ( RU ) Eurasian Community ЕАЭС RU С-IT.AA87.В.00765/21 CCVE 2021-07-29
Ex Emirates Certificate of Conformity D5000 ( EN ) United Arab Emirates 24-05-109026/E24-04-112697/NB0002 SGS 2024-05-02
Ex UL-cUL D5094, D5095, D5096, D5096-100, D5097 Divisions ( EN ) North America 20200226-E22230 UL 2020-02-28
Ex INMETRO Certificate DNV 13.0109 X for D5000 ( EN ) Brazil DNV 13.0109 X DNV 2022-12-10
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
IECEx DEKRA IECEx for D5000 Series ( EN ) International IECEx BVS 10.0072X DEKRA 2022-04-14
Maritime DNV Maritime Certificate TAA00001U0 for D5000 series for website ( EN ) International TAA00001U0 DNV-GL 2024-04-02
SIL TUV C-IS-272994-01 SIL Certificate Summary ( EN ) International C-IS-272994-01 TUV_SUD 2022-10-14

Declarations of Conformity


EU Declaration of Conformity for D5000 relays ( EN | IT )
EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
Declaration of Conformity G3 compliance ( EN )

Dimensions


Image of D5096_106_size

Connections


ACCESSORIES