I.S. SIL2 Switch/Proximity Relay-Out Repeater

The Switch/Proximity Detector Repeater D5232 is a module suitable for applications requiring SIL 2 level in safety related systems for high risk industries. The unit can be configured for switches or proximity detectors, located in Hazardous Area, and repeats the input state to a relay contact in Safe Area. The selectable fault detection circuit is available for proximity sensors or switches equipped with end-of-line resistors. Input-to-output function can be inverted, and signals can be duplicated.

FEATURES

  • SIL 2 / SC 3 (pending)
  • Input from Zone 0/Div. 1
  • Installation in Zone 2/Div. 2
  • High output current
  • Field open and short circuit detection
  • Input inversion available
  • Duplication available
  • Three port isolation, Input/Output/Supply
  • High Density, four channels per unit

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

Request a free and personalized quotation!

Technical Data


Supply

Voltage 24 Vdc nom (18 to 30 Vdc), reverse polarity protected.
Current Consumption 75 mA @ 24 Vdc with short circuit input and output closed, typical.
Power Dissipation 1.8 W @ 24 Vdc with short circuit input and output closed, typical, excluding output contact dissipation.

Input

Type Voltage source according to NAMUR standard.
Input equivalent source 7.5 V/1 kΩ typical (7.5 V no load, 7.5 mA short).
Input switching current levels ON ≥ 2.1 mA, OFF ≤ 1.2 mA.
No Fault input current ≥ 0.35 mA and input resistance ≥ 360 Ω.
Open Fault input current ≤ 0.05 mA.
Short fault input resistance ≤ 100 Ω.

Output

Type Voltage free SPST relay contact.
Contact material AgNi90/10.
Contact rating 2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load).
Mechanical / electrical life 15 * 10⁶ / 10 * 10⁴ operation, typical.
Input-output delay 20 ms, maximum.
Frequency response 10 Hz, maximum.

Isolation

Test Voltage I.S. In/Out 2.5 kV; I.S. In/Supply 2.5 kV; Out/Supply 500 V; Out/Out 500 V.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Storage temperature temperature limits –45 to +80 °C.

Safety description

Equipment Associated apparatus and non-sparking electrical equipment.
Safety parameters Uo = 11.2 V, Io = 12 mA, Po = 34 mW at terminals 13-14, 15-16, 17-18, 19-20. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C.

Mounting

Type DIN-Rail 35 mm, with or without Power Bus.
Weight about 175 g.
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
Dimensions Width 22.5 mm, Depth 123 mm, Height 120 mm.

Data Sheet


Datasheet of D5232 ( EN )

Instruction Manual


Instruction Manual D5232 ( EN )
ATEX safety instruction manual for D5000 series ( EN | IT )
UL Control Drawing D5232 ( EN )

Certifications


Type Description Area Number Issued by Issue Date
ATEX UL ATEX D5232, D5233 Series English Certificate ( EN ) Europe UL 24 ATEX 3258X UL 2024-11-08
Ex UL-cUL D5232, D5233 Divisions and Zones ( EN ) North America UL-US-2438735-0 UL 2024-11-14
IECEx UL IECEx D5232, D5233 Series English Certificate ( EN ) International IECEx ULD 24.0021X UL 2024-11-08
Maritime KR Maritime Certificate D5000 Series ( EN ) International MIL20769-EL002 KR 2024-06-26
Maritime DNV Maritime Certificate TAA00001U0 for D5000 series for website ( EN ) International TAA00001U0 DNV-GL 2024-04-02

Declarations of Conformity


EU Declaration of Conformity for D5232, D5233 ( EN | IT )
Declaration of Conformity G3 compliance ( EN )

Dimensions


Image of D5232_size

Connections


Software


SWC5090 - Configurator for D5000/D5200, D6000/D6200 Series isolators ( EN )