D5233Q G.M. International s.r.l.
GM International

D5233Q
I.S. SIL2 Switch/Proximity Transistor-Out Repeater

The Switch/Proximity Detector Repeater D5233 is a module suitable for applications requiring SIL 2 level in safety related systems for high risk industries. The unit can be configured for switches or proximity detectors, located in Hazardous Area, and repeats the input state to an open-collector transistor in Safe Area. The selectable fault detection circuit is available for proximity sensors or switches equipped with end-of-line resistors. Input-to-output function can be inverted, and signals can be duplicated.

FEATURES

  • SIL 2 / SC 3 (pending)
  • Input from Zone 0/Div. 1
  • Installation in Zone 2/Div. 2
  • High frequency transistor output
  • Field open and short circuit detection
  • Input inversion available
  • Duplication available
  • Three port isolation, Input/Output/Supply
  • High Density, four channels per unit

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

Request a free and personalized quotation!

Technical Data


Supply

Voltage 24 Vdc nom (18 to 30 Vdc), reverse polarity protected.
Current Consumption 45 mA @ 24 Vdc with short circuit input and output closed, typical.
Power Dissipation 1.1 W @ 24 Vdc with short circuit input and output closed, typical, excluding output contact dissipation.

Input

Type Voltage source according to NAMUR standard.
Input equivalent source 7.5 V/1 kΩ typical (7.5 V no load, 7.5 mA short).
Input switching current levels ON ≥ 2.1 mA, OFF ≤ 1.2 mA.
No Fault input current ≥ 0.35 mA and input resistance ≥ 360 Ω.
Open Fault input current ≤ 0.05 mA.
Short fault input resistance ≤ 100 Ω.

Output

Type Voltage free SPST optocoupled open-collector transistor.
Open-collector/drain rating 100 mA @ 35 V (≤ 1.5 V voltage drop).
Leakage current ≤ 50 µA @ 35 V.
Response time 1.5 ms, maximum.
Frequency response 1 kHz, maximum.

Isolation

Test Voltage I.S. In/Out 2.5 kV; I.S. In/Supply 2.5 kV; Out/Supply 500 V; Out/Out 500 V.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Storage temperature temperature limits –45 to +80 °C.

Safety description

Equipment Associated apparatus and non-sparking electrical equipment.
Safety parameters Uo = 11.2 V, Io = 12 mA, Po = 34 mW at terminals 13-14, 15-16, 17-18, 19-20. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C.

Mounting

Type DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board.
Weight about 175 g.
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
Dimensions Width 22.5 mm, Depth 123 mm, Height 120 mm.

Data Sheet


Datasheet of D5233 ( EN )

Instruction Manual


Instruction Manual D5233 ( EN )
ATEX safety instruction manual for D5000 series ( EN | IT )
UL Control Drawing D5233 ( EN )

Certifications


Type Description Area Number Issued by Issue Date
ATEX UL ATEX D5232, D5233 Series English Certificate ( EN ) Europe UL 24 ATEX 3258X UL 2024-11-08
Ex UL-cUL D5232, D5233 Divisions and Zones ( EN ) North America UL-US-2438735-0 UL 2024-11-14
IECEx UL IECEx D5232, D5233 Series English Certificate ( EN ) International IECEx ULD 24.0021X UL 2024-11-08
Maritime KR Maritime Certificate D5000 Series ( EN ) International MIL20769-EL002 KR 2024-06-26
Maritime DNV Maritime Certificate TAA00001U0 for D5000 series for website ( EN ) International TAA00001U0 DNV-GL 2024-04-02

Declarations of Conformity


EU Declaration of Conformity for D5232, D5233 ( EN | IT )
Declaration of Conformity G3 compliance ( EN )

Dimensions


Image of D5233_size

Connections


Software


SWC5090 - Configurator for D5000/D5200, D6000/D6200 Series isolators ( EN )