I.S. SIL2 Temperature Converter & Trip Amplifier
The Temperature Converter & Trip Amplifier D5273 accepts a low level dc signal from millivolt, thermocouple or 2-3-4 wire RTD or transmitting potentiometer sensors, located in Hazardous Area, and converts, with isolation, the signal to drive a Safe Area load, suitable for applications requiring SIL 2 level in safety related systems for high risk industries. Output signal can be direct or reverse. Modbus RTU RS-485 output is available on Bus connector. Cold junction compensation can be programmed as automatic, using an internal temperature sensor or fixed to a user-customizable temperature value. D5273S offers two independent trip amplifiers via two SPDT output relays.
FEATURES
- SIL 2 / SC 3
- Input from Zone 0/Div. 1
- Installation in Zone 2/Div. 2
- mV, TC, 2/3/4wire res./RTD or potentiometer input
- Two independent Trip Amplifiers (SPDT relay contacts)
- Inversion/scaling/custom output
- Selectable CJC: internal PT1000, external RTD or fixed
- Fastest integration time: 50 ms
- Burnout/internal/cjc/in sensor fault monitor
- Alarm output with user-settable trip points
- Modbus RTU RS-485 for monitor & configuration
- Fully programmable operating parameters
- High Accuracy, µP controlled A/D converter
- Three port isolation, Input/Output/Supply
STATUS
CHANNELS
1