D5290S-079 G.M. International s.r.l.
GM International

D5290S-079
SIL3 115 Vac Relay Out Module for 5 A NE/ND Loads

The D5290-079 is a relay module suitable for switching safety related circuits, up to SIL 3 level, for high risk industries. It provides isolation between input and output contacts. It makes available up to four NO contacts and two NC contacts, which can be externally connected for multiple Normally Energized (NE) or Normally De-energized (ND) loads, with single or both supply lines disconnection, and additional service loads. Compatibility with specific DO cards with pulse testing needs to be verified. This relay module is not suitable for low-current consumption applications (system-to-system signalling, driving LEDs, etc.).

FEATURES

  • SIL 3 / SC 3 for NE/ND loads with NE driver
  • Up to 5 A functional / 8 A inrush current
  • Load disconnection on both supply lines available
  • Service contact available
  • Multiple contacts (up to 4 NE or 2 ND loads)
  • Input/Output isolation

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

1

Request a free and personalized quotation!

Technical Data


Input

Type 115 Vac nom (95 to 130 Vac).
Current Consumption 25 mA @ 115 Vac, typical.
Power Dissipation 2.5 W @ 115 Vac, typical.

Output

Type 2 voltage free SPDT (= NO contact + parallel of 2 NC contacts) relay contacts identified with outputs: Out S_1 & Out P_1 and Out S_3 & Out P_2; 2 voltage free SPST (NO) relay contacts identified with: Out S_2 and Out S_4. Terminals 13-14 (Out S_1), 15-16 (Out S_2), 21-22 (Out S_4) and 23-24 (Out S_3) are: open when relay is de-energized, closed in energized relay condition. Terminals 17-18 (Out P_1) and 19-20 (Out P_2) are: closed when relay is de-energized, open in energized relay condition.
Contact material Ag Alloy (Cd free).
Contact rating 5 A 250 Vac 1250 VA, 5 A 250 Vdc 175 W (resistive load).
Contact inrush current 8 A @ 30 Vdc, 250 Vac.
Contact min. switching current 100 mA.
DC and AC load breaking capacity refer to Instruction Manual.
Mechanical / electrical life 10 * 10⁶ / 5 * 10⁴ operation, typical.
Operate / release time 12 ms / 4 ms, typical.

Isolation

Test Voltage Input/All Outs 2.5 kV; Out S_1 & Out P_1/Out S_3 & Out P_2, Out S_2, Out S_4 500 V; Out S_3 & Out P_2/Out S_2, Out S_4 500 V; Out S_2/Out S_4 500 V.

Environmental conditions

Operating temperature temperature limits -40 to +60 °C.
Storage temperature temperature limits -45 to +80 °C.

Mounting

Type DIN-Rail 35 mm.
Weight about 170 g.
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
Dimensions Width 22.5 mm, Depth 123 mm, Height 120 mm.

Data Sheet


Datasheet of D5290-079 ( EN | ES | DE | JA | CN | IT | FR | PT )
D5200 Series Common Specifications and Dimensional Drawing ( EN )

Instruction Manual


Instruction Manual D5290-079 ( EN )
Instruction Manual D5000-D5200 Series ( EN )

Certifications


Type Description Area Number Issued by Issue Date
EMC D5000/D6000 EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.PA08.B.82326/24 CONTROL 2024-09-26
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
Maritime DNV Maritime Certificate TAA00001U0 for D5000 series for website ( EN ) International TAA00001U0 DNV-GL 2024-04-02
Maritime KR Maritime Certificate D5000 Series ( EN ) International MIL20769-EL002 KR 2024-06-26
SIL TUV C-IS-224248-01 SIL Certificate Summary ( EN ) International C-IS-224248-01 TUV_SUD 2022-10-14

Declarations of Conformity


EU Declaration of Conformity for D5000 relays for Safe Area ( EN | IT )
EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
Declaration of Conformity G3 compliance ( EN )

Dimensions


Image of D5290_079_size

Connections


Drawings


3d_drawing_D5200_dwg ( EN )
3d_drawing_D5200_stp ( EN )