D5294S G.M. International s.r.l.
GM International

D5294S
SIL3 Relay Out Module for 5 A NE/ND Loads with LFD

The D5294 is a relay module suitable for switching safety related circuits, up to SIL 3 level, for high risk industries. It provides isolation between input and output contacts. It makes available 2+2 NO relay contacts connected in parallel and then in series to avoid spurious trip and to increase process availability. High process availability SIL 3 Safety Function for both Normally Energized (NE) and Normally De-energized (ND) / F&G loads is available. Load can be isolated from supply on both polarities. A wide compatibility towards different DCS/PLC is guaranteed: driving pulse testing is permitted by a dedicated internal circuit, which prevents contact and LED flickering. Line and load short/open circuit detection and load voltage monitoring are provided, both when the load is off and when the load is on. The fault in the field is directly mirrored to the PLC DO and it is also reported by opening the fault output. Diagnostic parameters are programmable and can also be monitored/configured through Modbus.

FEATURES

  • SIL 3 / SC 3 for NE/ND loads with NE/ND driver
  • SIL 2 / SC 3 for FAULT OUTPUTS
  • Installation in Zone 2/Div. 2
  • Up to 5 A functional / 6 A inrush current
  • Load disconnection on both supply lines available
  • High process availability to avoid spurious trips
  • Compatible with DCS/PLC pulse testing
  • Line and Load short/open circuit detection
  • Load voltage monitoring
  • Earth leakage monitoring
  • Internal coil integrity monitoring
  • Field fault mirroring to the PLC DO
  • Modbus RTU RS-485 for monitor & configuration
  • Service contact available
  • Input/Output/Supply isolation

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

1

Request a free and personalized quotation!

Technical Data


Supply

Type 24 Vdc nom (18 to 30 Vdc), reverse polarity protected.
Current Consumption 45 mA @ 24 Vdc (no fault), typical.
Power Dissipation 1.1 W @ 24 Vdc (no fault), typical.

Input

Type 24 Vdc nom (21.6 to 27.6 Vdc), reverse polarity protected. Relay coils are internally protected with suppressor diodes.
Current Consumption 40 mA @ 24 Vdc (no fault), typical.
Power Dissipation 1.0 W @ 24 Vdc (no fault), typical.

Output

Type Voltage free 2+2 SPST relay contact (2 paralleled contacts in series) at terminals 13-15 and 14-16, close when relay energized, open in de-energized condition.
Contact material Ag Alloy (Cd free), gold plated.
Contact rating 5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load).
Contact min. switching current 1 mA.
Contact inrush current 6 A @ 24 Vdc, 250 Vac.
DC and AC load breaking capacity refer to Instruction Manual.
Contact current derating refer to Instruction Manual.
Mechanical / electrical life 5 * 10⁶ / 3 * 10⁴ operation, typical.
Operate / release time 30 ms / 30 ms, typical.

Fault

Type Load & line short/open circuit, supply voltage and earth leakage monitor.
Diagnostics equivalent source when the load is off, the diagnostic circuit forces a sensing signal: 5.5 V open circuit, 10 mA short circuit, typical.
Line + load resistance programmable up to 50 kΩ.
Load current programmable up to 5 A.
Load supply voltage programmable up to 250 Vdc/Vac.
Load earth leakage programmable up to 3 MΩ.
Fault signaling voltage free DPST contact.
Fault 1 rating 0.5 A 30 Vac 15 VA, 0.5 A 50 Vdc 25 W (resistive load).
Fault 2 rating 3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W (resistive load).
Response time 4 s, typical.

Modbus interface

Type Modbus RTU RS-485 up to 115.2 kbps for monitor/configuration/control.

Isolation

Test Voltage Output/Input 2.5 kV; Output/Supply 2.5 kV; Output/Fault Outputs 2.5 kV; Output/RS485 Modbus 2.5 kV; Input/Supply 500 V; Input/Fault Output 1 500 V; Input/Fault Output 2 2.5 kV; Input/RS485 Modbus 500 V; Supply/Fault Output 1 500 V; Supply/Fault Output 2 2.5 kV; Supply/RS485 Modbus 500 V.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Storage temperature temperature limits -45 to +80 °C.

Mounting

Type DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board.
Weight about 195 g.
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
Dimensions Width 22.5 mm, Depth 123 mm, Height 120 mm.

Data Sheet


Datasheet of D5294 ( EN | FR | IT | PT | ES | DE | CN | JA )
D5200 Series Common Specifications and Dimensional Drawing ( EN )

Instruction Manual


Instruction Manual D5294 ( EN )
EAC safety instruction manual for D5000 series ( EN | RU )
Instruction Manual SWC5090 ( EN | RU )
Instruction Manual D5000-D5200 Series ( EN )
ATEX safety instruction manual for D5000 series ( EN | IT )
Safety Manual D5294 ( EN )
CCC Ex safety instruction manual for D5000 series ( EN | CN )
Ex safety instruction manual for D5000 series ( RU )
INMETRO safety instruction manual for D5000 series ( PT )
FM, FM-C Control Drawing D5293, D5294 ( EN )

Certifications


Type Description Area Number Issued by Issue Date
ATEX DEKRA ATEX D5000 Relay Series English Certificate ( EN ) Europe BVS 10 ATEX E 114 X DEKRA 2022-04-12
EMC D5000/D6000 EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.PA08.B.82326/24 CONTROL 2024-09-26
Ex D5000 CCC certificate for China ( EN ) China 2020322316000978 NEPSI 2024-03-22
Ex CCOE Indian Approval for D5293, D5294, D5295 ( EN ) India P424465 PESO 2020-07-23
Ex EAC Ex Certificate for D5000 Series ( RU ) Eurasian Community ЕАЭС RU С-IT.AA87.В.01310/24 CCVE 2024-06-13
Ex Emirates Certificate of Conformity D5000 ( EN ) United Arab Emirates 24-05-109026/E24-04-112697/NB0002 SGS 2024-05-02
Ex FM No.3046304-3046304C Certificate D5000 Series ( EN ) North America 3046304-3046304C FM 2013-04-09
Ex INMETRO Certificate DNV 13.0109 X for D5000 ( EN ) Brazil DNV 13.0109 X DNV 2022-12-10
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
IECEx DEKRA IECEx for D5000 Series ( EN ) International IECEx BVS 10.0072X DEKRA 2022-04-14
Maritime KR Maritime Certificate D5000 Series ( EN ) International MIL20769-EL002 KR 2024-06-26
Maritime DNV Maritime Certificate TAA00001U0 for D5000 series for website ( EN ) International TAA00001U0 DNV-GL 2024-04-02
SIL TUV C-IS-722160171 SIL Certificate Summary ( EN ) International C-IS-722160171 TUV_SUD 2022-10-14
SIL TUV C-IS-236198-04 SIL Certificate Summary ( EN ) International C-IS-236198-04 TUV_SUD 2022-10-14

Declarations of Conformity


EU Declaration of Conformity for D5000 relays ( EN | IT )
EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
Declaration of Conformity G3 compliance ( EN )
Declaration of Conformity (IECEx) for D5090S, D5091S, D5290S, D5291S, D5293S, D5294S. ( EN )

Dimensions


Image of D5294_size

Connections


Drawings


2d_drawing_D5200_dwg ( EN )
3d_drawing_D5200_dwg ( EN )
3d_drawing_D5200_stp ( EN )

Software


SWC5090 - Configurator for D5000/D5200, D6000/D6200 Series isolators ( EN )
Instruction Manual SWC5090 ( EN )