TB-D5008-BAI-003 G.M. International S.p.A.
GM International

TB-D5008-BAI-003

TB-D5008-BAI-003
7-pos Term. Board for AO cards Bailey INFI 90 IMASO01/IMASO11 & ABB Symphony SPASO11

This Termination Board (TB) provides direct connection between the I/O Card of the system and D5000 / D6000 Series modules. The Intrinsically Safe protection and signal isolation between Safe and Hazardous Area is provided by D5000 Series Associated Apparatus. The 24 Vdc Power Supply of the TB is connected to two plug-in terminal blocks, for a redundant power supply.

FEATURES

  • Bailey INFI 90 AO Cards board interface
  • Connection to external GMI HART Mux 5700(-110)
  • 7 positions Termination Board for up to 14 channels
  • Lower cables installation and maintenance costs
  • Power supplies fault monitoring
  • Hardware kit provided for single DIN Rail or wall mounting

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

14

Request a free and personalized quotation!

Technical Data


General

Number of positions 7
Maximum number of channels 14

Supply

Type 24 Vdc nom (20 to 30 Vdc), reverse polarity protected, double terminal blocks for redundant power supply, with OR diodes to mix supply voltages.
Max allowed current consumption 1 A (as total supply).
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm².
Protection fuse 2 A time lag.

Fault detection

Type module cumulative fault. Any malfunction is reported by deactivating a relay and activating the corresponding LEDs.
Alarm is issued if:
1) Power supply 1 or 2 < 17 Vdc or
2) Power supply 1 or 2 > 33 Vdc or
3) Module cumulative fault ON.
Alarm is removed if:
1) 20 Vdc < Power supply 1 and 2 < 30 Vdc and
2) No module cumulative fault.
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm².
Output rating 2 A 36 Vac 72 VA, 2 A 48 Vdc 80 W (resistive load).

I/O Card Interface

Connection one 36 poles AMP640506 male connector (requiring female mating connector).

HART Mux Interface

Connection one 34-poles receptacle connector (require female mating connector).
Cable flat cable CABF032.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Max altitude 2000 m a.s.l.
Storage temperature temperature limits –45 to +80 °C.

Mounting

Type Hardware included for mounting on wall and single DIN rail.
Weight about 220 g (excluding modules and mounting options).
Location installation in Safe Area.
Dimensions Width 165 mm, Depth 176 mm, Height 125 mm.

Data Sheet


Datasheet of TB-D5008-BAI-003 ( EN )
ABB Bailey Infi 90 TB Summary ( EN | CN | JA | IT | PT | ES | DE | FR )

Certifications


Type Description Area Number Issued by Issue Date
EMC 5700 and TB EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.PA08.B.82359/24 CONTROL 2024-09-26

Declarations of Conformity


EU Declaration Termination Boards TB, TBE, TUE ( EN | IT )
Declaration of Conformity G3 compliance ( EN )

Dimensions