TB-D5016-HON-004 G.M. International s.r.l.
GM International

TB-D5016-HON-004
Termination Board 16 positions for Honeywell Safety Manager Analog Input Card SAI-1620m

This Termination Board (TB) provides direct connection between the I/O Card of the system and D5000 Series modules. The Intrinsically Safe protection and signal isolation between Safe and Hazardous Area, is provided by D5000 Series Associated Apparatus. 24 Vdc Supply to the TB can be provided by dedicated system screws or by two plug-in terminal blocks, for a redundant power supply. The power supply for modules is given by TB power bus.

FEATURES

  • Support for Honeywell Safety Manager SAI-1620m 16 ch. AI Card
  • 16 positions Terminal Board for up to 32 channels.
  • Lower cables installation and maintenance costs.
  • Power supplies fault monitoring.
  • Spare fuse provided.
  • Mounting hardware provided for: Wall mounting, M4 thread screw; Wall mounting, M4 self tapping screw; Single Din Rail mounting kit.

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

16 or 32

Request a free and personalized quotation!

Technical Data


Supply

Voltage 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, double terminal blocks for redundant power supply, with OR diodes to mix supply voltages. Alternatively via dedicated Screws from Honeywell System.
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm2.
2 LEDs indication green color, one for supply 1 and one for supply 2.
Protection fuse 2 A time lag (spare fuse provided on Termination Board).

Fault detection

1) Abnormal supply voltage supply 1 or supply 2 is < 18 Vdc (Under Voltage, UV) or > 30 Vdc (Over Voltage, OV).
2) Cumulative module fault at least one of the modules reports a field/internal fault

LED fault signaling (for both case 1 and 2)

Type 1 red LED for abnormal supply 1; 1 red LED for abnormal supply 2; a cumulative module fault red LED.
Relay fault signaling (one for each case 1 or 2) a voltage free NE SPDT - 1 Form C relay contacts (de-energized in fault condition)
Contact material AgCdO.
Contact rating 2 A 36 Vac 72 VA, 2 A 48 Vdc 80 W (resistive load).
Mechanical / electrical life 30 * 106 / 1 * 105 operation, typical.
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm2.

I/O Card Interface

Connection two 20 poles male connectors (require female mating connectors).

HART Multiplexing

Connection two 34 poles male connectors (require female mating connectors).

Environmental conditions

Operating temperature limits – 40 to + 70 °C, relative humidity max 90 % non condensing, up to 35 °C.
Storage temperature limits – 45 to + 80 °C.

Mounting

Type Hardware included for mounting on wall and single DIN rail.
Weight about 400 g (excluding modules and mounting options).
Location Safe Area / Ordinary locations.
Dimensions Width 275 mm, Depth 175 mm, Height 125 mm.

Data Sheet


Datasheet of TB-D5016-HON-004 ( EN )
Honeywell Safety Manager TB Summary ( EN )

Certifications


Type Description Area Number Issued by Issue Date
EMC 5700 and TB EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.PA08.B.82359/24 CONTROL 2024-09-26

Declarations of Conformity


EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
EU Declaration Termination Boards TB, TBE, TUE ( EN )
Declaration of Conformity G3 compliance ( EN )

Dimensions