TB-D5016-YOK-007 G.M. International s.r.l.
GM International

TB-D5016-YOK-007
Termination Board 16 positions for Yokogawa Prosafe RS with Digital Input card SDV144

This Termination Board (TB) provides direct connection between the I/O Card of the system and D5000 Series modules. The Intrinsically Safe protection and signal isolation between Safe and Hazardous Area is provided by D5000 Series Associated Apparatus. The 24 Vdc Power Supply of the TB is connected to two plug-in terminal blocks, for a redundant power supply. The power supply for modules is given by TB power bus.

FEATURES

  • 2 x DI card type SDV144 (16 channels) Digital Input board interface.
  • 16 positions Terminal Board for up to 32 channels.
  • Lower cables installation and maintenance costs.
  • Power supplies fault monitoring.
  • Spare fuse provided.
  • Mounting hardware provided for: Single Din Rail mounting kit; Wall mounting, M4 self tapping screw; Wall mounting, M4 thread screw.

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

16 or 32

Request a free and personalized quotation!

Technical Data


Supply

Voltage 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, double terminal blocks for redundant power supply, with OR diodes to mix supply voltages.
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm2.
Protection fuse 4 A slow blow (spare fuse provided on Termination Board).

Fault detection

Type (for more information see Fault Logic section)
Abnormal supply voltages or module cumulative fault PWR 1 or PWR 2 is in under (< 18 Vdc) or over (> 30 Vdc) voltage condition OR module cumulative fault indication.
Relay fault signaling a voltage free NE SPST-1 Form A relay contact (de-energized in fault condition)
Contact material AgCdO.
Contact rating 2 A 36 Vac 72 VA, 2 A 48 Vdc 80 W (resistive load).
Mechanical / electrical life 30 * 106 / 1 * 105 operation, typical.
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm2.
LED fault signaling 1 green LED (PWR 1 OK); 1 green LED (PWR 2 OK); 1 red LED (UV or OV of PWR 1); 1 red LED (UV or OV of PWR 2); a cumulative fault red LED.

Prosafe RS I/O card interface

Connection four 50 poles male connectors (require female mating connectors).

Field signal

Connection directly to module by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm2.

Environmental conditions

Operating temperature limits – 40 to + 70 °C, relative humidity max 90 % non condensing, up to 35 °C.
Storage temperature limits – 45 to + 80 °C.

Mounting

Type Hardware included for mounting on wall and single DIN rail.
Weight about 400 g (excluding modules and mounting options).
Location Safe Area / Ordinary locations.
Dimensions Width 267 mm, Depth 176 mm, Height 125 mm.

Data Sheet


Datasheet of TB-D5016-YOK-007 ( EN )
Yokogawa Prosafe RS & Centum VP TB Summary ( EN )

Certifications


Type Description Area Number Issued by Issue Date
EMC 5700 and TB EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.PA08.B.82359/24 CONTROL 2024-09-26

Declarations of Conformity


EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
EU Declaration Termination Boards TB, TBE, TUE ( EN )
Declaration of Conformity G3 compliance ( EN )

Dimensions