X1-TB-16-GMI-02 G.M. International S.p.A.
GM International

X1-TB-16-GMI-02

X1-TB-16-GMI-02
16-pos X1-Series Digital Term. Board

This Termination Board (X1-TB) provides direct connection between the I/O Card of the system and X1-Series modules. Galvanic isolation or conditioning is provided by X1-Series Repeaters/Converters (X1-NIS). The 24 Vdc Power Supply of the X1-TB is connected to two connectors, for redundant power supply. A monitoring circuit activates a cumulative fault in case of supply or module failure. X1-GW series also provides module identification, configuration and monitoring.

FEATURES

  • Digital Card board interface for up to 16 channels
  • Lower cables installation and maintenance costs
  • Power supplies fault monitoring
  • Single loop disconnection to ease maintenance operations
  • X1-GW Gateway for data reading, id/config/monitor/HART®
  • Input-to-Output isolation

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

Request a free and personalized quotation!

Technical Data


General

Number of positions/channels 16
Power Dissipation 0.55 W @ 24 Vdc without modules, typical.

Supply

Type 24 Vdc nom (20 to 28.8 Vdc), reverse polarity protected, double terminal blocks for redundant power supply, with OR diodes to mix voltages.
Current Consumption 23 mA @ 24 Vdc without modules, typical.
Max current consumption 1.5 A (as total supply), 4 A time-lag fuse protected.
Connection by polarized plug-in disconnect screw terminal blocks.

Fault

Type The on-board diagnostic monitors both power supplies integrity and the module failures. Any malfunction is reported by deactivating a solidstate relay and activating the corresponding LEDs.
Cumulative alarm is issued if:
1) Power supply 1 or 2 < 17 Vdc or > 33 Vdc or
2) Any module failure active.
Cumulative alarm is removed if:
1) 20 Vdc < Power supply 1 and 2 < 30 Vdc and
2) No module failure.
Connection by polarized plug-in disconnect screw terminal blocks.
Ratings 100 mA 35 V (≤ 1 V voltage drop).

Field Interface

Connection 100 mA 35 V (≤ 1 V voltage drop).

Isolation

Test Voltage by polarized plug-in disconnect 8-position screw or pushin spring terminal blocks.

Environmental conditions

Operating temperature Field/System Interface (through Gateway) 2.5 kV; Field/Supply 2.5 kV; Field Ch/Ch 1.5 kV.
Max altitude temperature limits –40 to +70 °C.
Storage temperature 2000 m a.s.l.

Mounting

Type temperature limits –45 to +80 °C.
Weight about 670 g, excluding modules.
Location Safe Area.
Dimensions Width 244 mm, Depth 143 mm, Height 155 mm.

Data Sheet


Datasheet of X1-TB-16-GMI-02 ( EN )

Instruction Manual


Instruction Manual X1 Series ( EN )
Instruction Manual of X1-TB-16-GMI-02 ( EN )

Declarations of Conformity


EU Declaration of Conformity of X1-TB-16-GMI-02 ( EN | IT )

Dimensions


Image of X1-TB-16-GMI-02_size

Connections