X1-TB-16-HON-01 G.M. International S.p.A.
GM International

X1-TB-16-HON-01
SIL3 16-pos X1-Series Term Board for Safety Manager SC PUIO01 and PDIO01 Card

This Termination Board (X1-TB) provides direct connection between the I/O Card of the system and X1-Series modules. Galvanic isolation or conditioning is provided by Repeaters/Converters (X1-NIS). The 24 Vdc Power Supply of the X1-TB is connected to two plug-in terminal blocks, for redundant power supply. A monitoring circuit activates a cumulative fault in case of supply or module failure. The board can host a gateway belonging to the X1-GW series for module identification, configuration and monitoring.

FEATURES

  • SIL 3 / SC 3
  • UIO Card board interface for up to 16 channels
  • Lower cables installation and maintenance costs
  • Power supplies fault monitoring
  • Single loop disconnection to ease maintenance operations
  • X1-GW Gateway optional for id/config/monitor/HART®
  • Three port isolation, Input/Output/Supply

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

Request a free and personalized quotation!

Technical Data


General

Number of positions/channels 16
Power Dissipation 0.43 W @ 24 Vdc without modules, typical.

Supply

Voltage 24 Vdc nom (20 to 28.8 Vdc), reverse polarity protected, double terminal blocks for redundant power supply, with OR diodes to mix voltages.
Current Consumption 18 mA @ 24 Vdc without modules, typical.
Max current consumption 1.5 A (as total supply), 4 A time-lag fuse protected.
Connection by polarized plug-in disconnect screw terminal blocks.

Fault

Type The on-board diagnostic monitors both power supplies integrity and the module failures. Any malfunction is reported by deactivating a solidstate relay and activating the corresponding LEDs.
Cumulative alarm is issued if:
1) Power supply 1 or 2 < 17 Vdc or > 33 Vdc or
2) Any module failure active.
Cumulative alarm is removed if:
1) 20 Vdc < Power supply 1 and 2 < 30 Vdc and
2) No module failure.
Connection by polarized plug-in disconnect screw terminal blocks.
Ratings 100 mA 35 V (≤ 1 V voltage drop).

Field Interface

Connection by polarized plug-in disconnect 8-position screw or pushin spring terminal blocks.

System interface

Type The system interface sinks current, hence it requires source I/O cards.
Connection one SUB-D 37 poles male connector (requiring female mating connector).
Cable FS-SICC5xxx.

Isolation

Test Voltage Field/System 2.5 kV; Field/Supply 2.5 kV; System/Supply 500 V; Field Ch/Ch 1.5 kV.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Max altitude 2000 m a.s.l.
Storage temperature temperature limits –45 to +80 °C.

Mounting

Type On single DIN-rail 35 mm.
Weight about 730 g, excluding modules.
Location Safe Area.
Dimensions Width 244 mm, Depth 143 mm, Height 155 mm.

Data Sheet


Datasheet of X1-Series Honeywell Safety Manager SC Summary ( EN )
Datasheet of X1-TB-16-HON-01 ( EN )

Instruction Manual


Instruction Manual of X1-TB-16-HON-01 ( EN )

Declarations of Conformity


EU Declaration of Conformity of X1-TB-16-HON-01 ( EN | IT )

Dimensions


Image of X1-TB-16-HON-01_size

Connections