Description
The single channel Switch/Proximity Detector Interface, D5034S, is a high integrity repeater, designed to interface contacts or proximity detectors (EN60947-5-6, NAMUR) located in Hazardous Area and is suitable for applications requiring SIL 3 level (according to IEC 61508) in safety related systems for high risk industries.
Field loop integrity and status (line plus contact or proximitor) are continuously and directly monitored, in transparent mode, into the PLC, ESD, DCS using their existing input line, without requiring an additional channel for line fault detection.
Mounting on standard DIN-Rail, with or without Power Bus, or on customized Termination Boards, in Safe Area or in Zone 2.
Features
• Input from Zone 0 (Zone 20), installation in Zone 2.
• Transparent mode operation.
• Field open and short circuit detection available to the PLC/DCS card.
• Input and Output short circuit proof
• High Accuracy.
• Three port isolation, Input/Output/Supply.
• EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
• High Density, two channels per unit.
• Simplified installation using standard DIN-Rail and plug-in terminal blocks, with or without Power Bus, or customized Termination Boards.
• 250 Vrms (Um) max. voltage allowed to the
Supply
18-30 Vdc
Channels
1 (
2 channels: D5034D )
SIL level
SIL 3