TB-D5001-HRT-003 G.M. International s.r.l.
GM International

TB-D5001-HRT-003

TB-D5001-HRT-003
SIL 3 HART® Multiplexer Termination Board 1 position for up to 64 channels (extendable to 256 channels)

The HART® Termination Board model TB-D5001-HRT-003 allows the remote monitoring of any HART®-compatible 4/20 mA field loop. This is obtained by one locally mounted HART® Multiplexer Modem 5700 series and by interface connectors to access the relevant loops. The single TB-D5001-HRT-003 Termination Board supports 64 channels. Yet, it could be extended with additional TB-D5001-HRT-003 units (up to 4) to manage all 256 channels available on the HART® Multiplexer Modem 5700 series. The Mux unit connects, via the RS-485 interface, to an external PC running an FDTbased software package (PACTware™, etc...) through a dedicated Device Type Manager (DTM). The PC can communicate with multiple Mux units, located on different boards, in a multi-drop RS-485 mode. The HART® Termination Board TB-D5001-HRT-003 is SIL 3 certified as non-interfering with the signal loops.

FEATURES

  • SIL 3 according to IEC 61508:2010 Ed. 2 (see Safety Manual ISM0436 for more information).
  • Systematic capability SIL 3.
  • HART® Multiplexing Board of up to 64 analog signals (extendable to 256 channels with 3 additional TB-D5001-HRT-003 units).
  • Redundant Power Supply connection by screw terminals.
  • Supply is fuse protected and with LED indication.
  • Dedicated terminal to connect RS-485 communication cable shield.
  • RS-485 interface terminals to communicate with the HART® Mux unit.
  • HART® channels isolated with dual capacitors (short circuit proof).
  • Spare fuse provided.
  • Includes hardware for Easy installation in three modes: Wall mounting, M4 Threads, Wall mounting, Self Threading, Din Rail mounting.

STATUS

 
   PHASE-OUT
Next: SPARE-ONLY (2029-01-01)

Product lifecycle policy (EN)

ALTERNATIVE PRODUCT

CHANNELS

64

Request a free and personalized quotation!

Technical Data


Supply

Voltage 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, redundant terminal blocks, OR diodes to select higher supply source.
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm2.
2 LEDs indication green.
Protection fuse 2 A time lag (spare fuse provided on Termination Board).

HART Interface

Connection 4 flat cable 34 poles male connectors (requires female mating connector).
DC Isolation dual capacitor for each channel.
Common mode voltage up to 50 V.

Additional TBs interface

Connection flat cable 10 poles male connectors (requires female mating connector).

Environmental conditions

Operating temperature limits – 40 to + 70 °C, relative humidity 95 %, up to 55 °C.
Storage temperature limits – 45 to + 80 °C.

Approvals

Type SIL 3 conforms to IEC61508:2010 Ed.2.

Mounting

Surface (Wall) or DIN Rail mounting TB-OPT-001 is a Kit including hardware for mounting on wall and DIN rail.
Weight about 200 g (excluding modules and mounting options
Location installation in Safe Area or Ordinary Location.
Dimensions Width 176 mm, Depth 147 mm, Height 125 mm.

Data Sheet


Datasheet of TB-D5001-HRT-003 ( EN )

Instruction Manual


Instruction Manual HART Mux modem 5700 ( EN | RU )
Safety Manual 5700-xxx + TB-D5001-HRT-003, -004, -005, -006, -007 ( EN )

Certifications


Type Description Area Number Issued by Issue Date
EMC 5700 and TB EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.АЖ38.В.00125/19 EUROCERT 2019-05-30
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
SIL TUV C-IS-272994-01 SIL Certificate Summary ( EN ) International C-IS-272994-01 TUV_SUD 2022-10-14

Declarations of Conformity


EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
EU Declaration Termination Boards TB, TBE, TUE ( EN )
Declaration of Conformity G3 compliance ( EN )

Dimensions