D1010S-046 G.M. International s.r.l.
GM International

D1010S-046
SIL 2 Repeater Power Supply Smart-HART® compatible DIN-Rail

The single and dual channel DIN Rail Repeater Power Supply, D1010S-046 and D1010D-046, provides a fully floating dc supply for energizing conventional 2 wires 4-20 mA transmitters, or separately powered 3, 4 wires 4-20, 0-20 mA transmitters located in Hazardous Area, and repeats the current in floating circuit to drive a Safe Area load. The circuit allows bi-directional communication signals, for HART®-Smart transmitters.

FEATURES

  • SIL2 /SC3
  • Input from Zone 0 (Zone 20), installation in Zone 2.
  • High Density, two channels per unit.
  • 4-20 or 0-20 mA Input, Output Signal.
  • Wide Band Smart Communication, HART® compatible.
  • Input and Output short circuit proof.
  • High Accuracy.
  • Three port isolation, Input/Output/Supply.
  • EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1
  • In-field programmability by DIP Switch.
  • 250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.

STATUS

 
   PHASE-OUT
Next: SPARE-ONLY (2027-01-01)

Product lifecycle policy (EN)

CHANNELS

1

Request a free and personalized quotation!

Technical Data


Supply

Type 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp.
Current Consumption 60 mA @24V with 20 mA output typical.
Power Dissipation 1.9 W with 24 V supply voltage and 20 mA output typical.
Max. power consumption 2.0 W at 30 V supply voltage and short circuit condition

Input

Type 0/4 to 20 mA (separately powered input, voltage drop ≤ 0.9 V) or 4 to 20 mA (2 wire Tx current limited at ≈ 25 mA).
Transmitter line voltage ≥ 15.0 V at 20 mA with max. 20 mVrms ripple on 0.5 to 40 KHz frequency band.

Output

Type 0/4 to 20 mA, on max. 600 Ω load in source mode; V min. 5 V at 0 Ω load V max. 30 V in sink mode, current limited at ≈ 23 mA or 0/1 to 5 V on internal 250 Ω shunt (or 0/2 to 10 V on internal 500 Ω shunt on request).
Response time 50 ms (10 to 90 % step change).
Output ripple ≤ 20 mVrms on 250 Ω communication load on 0.5 to 40 KHz band.
Frequency response 0.5 to 40 KHz bidirectional within 3 dB (HART® and higher frequency protocols).

Performance

Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
Calibration accuracy ≤ ± 0.1 % of full scale.
Linearity error ≤ ± 0.05 % of full scale.
Supply voltage influence ≤ ± 0.05 % of full scale for a min to max supply change.
Load influence ≤ ± 0.05 % of full scale for a 0 to 100 % load resistance change.
Temperature influence ≤ ± 0.01 % on zero and span for a 1 °C change.

Isolation

Test Voltage I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V.

Safety description

Equipment Associated apparatus and non-sparking electrical equipment
Safety parameters Uo/Voc = 26.3 V, Io/Isc = 91 mA, Po/Po = 597 mW at terminals 14-15, 10-11. Uo/Voc = 1.1 V, Io/Isc = 38 mA, Po/Po = 11 mW at terminals 15-16, 11-12. Ui/Vmax = 30 V, Ii/Imax = 104 mA, Ci = 1.05 nF, Li = 0 nH at terminals 15-16, 11-12. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C.

Environmental conditions

Operating temperature temperature limits -20 to + 60 °C, relative humidity max 95 %.
Storage temperature temperature limits -45 to + 80 °C.

Mounting

Type EN/IEC60715 TH 35 DIN-Rail.
Weight 125 g
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm2.
Location Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
Protection class IP 20.
Dimensions Width 22.5 mm, Depth 99 mm, Height 114.5 mm.

Data Sheet


Datasheet of D1010-046 ( EN )
D1000 Series Common Specifications and Dimensional Drawing ( EN )

Instruction Manual


Instruction Manual D1010-046 ( EN )
Instruction Manual D1000 Series ( EN | RU )
Ex safety instruction manual for D1000 series ( EN | IT )
INMETRO safety instruction manual for D1000 series ( PT )

Certifications


Type Description Area Number Issued by Issue Date
ATEX DEKRA ATEX D1000 Series English Certificate ( EN ) Europe DMT 01 ATEX E 042 X DEKRA 2022-04-25
ATEX IMQ Zone 2 Applications D1000 Series Certificate ( EN ) Europe IMQ 09 ATEX 013 X IMQ 2022-05-03
EMC D1000 EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.НХ37.В.06311/20 EUROCERT 2020-08-13
Ex EAC Ex Certificate for D1000 Series ( RU ) Eurasian Community ЕАЭС RU С-IT.НА67.В.00113/20 TECHNOPROGRESS 2020-09-04
Ex INMETRO Certificate DNV 13.0108 X for D1000 series ( EN ) Brazil DNV 13.0108 X DNV 2022-12-10
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
IECEx IMQ IECEx Zone 2 Applications D1000 Series Certificate ( EN ) International IECEx IMQ 13.0011X IMQ 2022-05-03
IECEx DEKRA IECEx for D1000 Series ( EN ) International IECEx BVS 07.0027X DEKRA 2022-05-30
Maritime KR Maritime Certificate D1000 Series ( EN ) International MIL20769-EL001 KR 2022-07-04
Maritime DNV Maritime Certificate TAA00002BM for D1000 Series ( EN ) International TAA00002BM DNV-GL 2024-04-05
Metrological Metrological Certificate Russia for D1000 Series ( RU ) Russia 64283-11 ROSSTANDART 2021-03-10
SIL TUV C-IS-236198-03 SIL Certificate Summary ( EN ) International C-IS-236198-03 TUV_SUD 2022-10-14

Declarations of Conformity


EU Declaration of Conformity D1000 series ( EN | IT )
EU Declaration of Conformity for D1000 series (zone 2) ( EN | IT )
EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
Declaration of G3 compliance for D1000_PSD1000-PSD1001-PSD1001C-PSD1004-PSD1220-PSD1220-098 SERIES ( EN )

Dimensions


Image of D1010S-D1010D_size

Connections


Drawings


2d_drawing_D1000_dwg ( EN )
3d_drawing_D1000_dwg ( EN )
3d_drawing_D1000_stp ( EN )

RELATED PRODUCTS