Input |
Type
|
Loop powered control signal.
|
Voltage
|
24 Vdc nom (20 to 30 Vdc), reverse polarity protected.
|
Current Consumption
|
65 mA @ 24 Vdc with 45 mA output, typical, ≤ 10 mA when fault circuit enabled and fault condition detected.
|
Power Dissipation
|
1.1 W @ 24 Vdc with 45 mA output, typical.
|
Override input |
Type
|
Override control signal de-energizes output when enabled by dip-switch.
|
Voltage
|
0 V ≤ OFF ≤ 5 V, 20 V ≤ ON ≤ 30 V, reverse polarity protected.
|
Current Consumption
|
15 mA @ 24 Vdc, typical.
|
Output |
Type
|
45 mA @ 13.0 V (21.0 V no load, 174 Ω series resistance) at terminals 7-10 Out A.
45 mA @ 10.2 V (21.0 V no load, 236 Ω series resistance) at terminals 8-10 Out B.
45 mA @ 8.5 V (21.0 V no load, 275 Ω series resistance) at terminals 9-10 Out C.
|
Short circuit current
|
≥ 50 mA, 55 mA typical
|
Output diagram
|
refer to Instruction Manual.
|
Response time
|
≤ 75 ms.
|
Fault |
Type
|
Field device and wiring open circuit or short circuit detection dip-switch
selectable. When fault is detected, output is de-energized until normal
condition is restored.
|
Short output
|
load resistance ≤ 50 Ω (≈ 2 mA forcing to detect fault).
|
Open output
|
load resistance > 10 kΩ.
|
Fault signaling
|
voltage free NE SPST optocoupled open-collector
transistor (output de-energized in fault condition).
|
Open-collector/drain rating
|
100 mA @ 35 Vdc (≤ 1.5 V voltage drop).
|
Leakage current
|
≤ 50 μA @ 35 Vdc.
|
Response time
|
≤ 75 ms.
|
Isolation |
Test Voltage
|
I.S. Out/In 2.5kV; I.S. Out/Fault 2.5kV; I.S. Out/Override 2.5kV; In/Fault 500
V; In/Override 500 V; Fault/Override 500 V.
|
Environmental conditions |
Operating temperature
|
temperature limits –40 to +70 °C
|
Storage temperature
|
temperature limits –45 to +80 °C.
|
Safety description |
Equipment
|
Associated apparatus and non-sparking electrical equipment.
|
Safety parameters
|
Uo = 24.8 V, Io = 147 mA, Po = 907 mW at terminals 7-10 Out A.
Uo = 24.8 V, Io = 108 mA, Po = 667 mW at terminals 8-10 Out B.
Uo = 24.8 V, Io = 93 mA, Po = 571 mW at terminals 9-10 Out C.
Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C.
|
Mounting |
Type
|
DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board.
|
Weight
|
about 130 g.
|
Connection
|
by polarized plug-in disconnect screw terminal blocks to
accomodate terminations up to 2.5 mm² (13 AWG).
|
Dimensions
|
Width 12.5 mm, Depth 123 mm, Height 120 mm.
|