D6231E G.M. International s.r.l.
GM International

D6231E
SIL2 Switch/Proximity O.C.-Out Repeater

The Switch/Proximity Detector Repeater D6231 is a module suitable for applications requiring SIL 2 level in safety related systems for high risk industries. The unit can be configured for switches or proximity detectors and repeats the input state to a solid-state relay contact. The selectable fault detection circuit is available for proximity sensors or switches equipped with end of line resistors. The module is fully configurable to achieve input/output multiplexing, duplication, inversion, and input logical elaboration (AND, OR). Each output can also be configured to report the cumulative fault of any input subset. Configuration and diagnostic parameters are programmable and can also be monitored/set through Modbus.

FEATURES

  • SIL 2 / SC 3
  • Field open and short circuit detection
  • Input muxing/duplication/inversion/operations available
  • Modbus RTU RS-485 for monitor & configuration
  • Fully programmable operating parameters
  • Three port isolation, Input/Output/Supply
  • High Density, eight channels per unit

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

8

Request a free and personalized quotation!

Technical Data


Supply

Type 24 Vdc nom (18 to 30 Vdc), reverse polarity protected.
Current Consumption 84 mA @ 24 Vdc with short circuit input and output closed, typical.
Power Dissipation 2.1 W @ 24 Vdc with short circuit input and output closed, typical.

Input

Type NAMUR standard according to IEC 60947-5-6
Input switching current levels ON ≥ 2.1 mA, OFF ≤ 1.2 mA.
Open Fault current ≤ 0.05 mA.
Short fault resistance ≤ 100 Ω.
No Fault current ≥ 0.35 mA and resistance ≥ 360 Ω.
Input equivalent source 8 V 1 kΩ typical (8 V no load, 8 mA short).

Output

Type Voltage free SPST optocoupled open-collector transistor (solid-state relay, photo-MOS).
Open-collector/drain rating 100 mA @ 35 V (≤ 1.0 V voltage drop).
Leakage current ≤ 10 µA @ 35 V.
Response time 2 ms.
Frequency response 500 Hz maximum.

Modbus interface

Type Modbus RTU RS-485 up to 115.2 kbps for monitor/configuration/control.

Isolation

Test Voltage In/Out 1.5 kV; In/Supply 1.5 kV; Out/Supply 500 V.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Storage temperature temperature limits –45 to +80 °C.

Mounting

Type DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board.
Weight about 175 g.
Connection by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm² (13 AWG).
Dimensions Width 22.5 mm, Depth 123 mm, Height 120 mm.

Data Sheet


Datasheet of D6231 ( EN | FR | JA | IT | ES | DE | RU | CN | PT )

Instruction Manual


Instruction Manual D6231 ( EN )
Safety Manual of D6231E ( EN )

Certifications


Type Description Area Number Issued by Issue Date
EMC D5000/D6000 EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.PA08.B.82326/24 CONTROL 2024-09-26
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25

Dimensions


Image of D6231_size

Connections


Drawings


2d_drawing_D5200_dwg ( EN )
3d_drawing_D5200_dwg ( EN )
3d_drawing_D5200_stp ( EN )

Software


SWC5090 - Configurator for D5000/D5200, D6000/D6200 Series isolators ( EN )
Instruction Manual SWC5090 ( EN )