Termination Board 16 positions for
Invensys FBM200 with
Digital Output card FBM242
This Termination Board (TB) provides direct connection between the I/O Card of the system and D5000 Series modules. The Intrinsically Safe protection and signal isolation between Safe and Hazardous Area, is provided by D5000 Series Associated Apparatus. The 24 Vdc Power Supply of the TB is connected to two plug-in terminal blocks, for a redundant power supply. The power supply for modules is given by TB power bus. The TB-D5016-INV-003-2 adds to the TB-D5016-INV-003 the possibility of disconnecting individually each actuator and the capability of switching off the actuators through a safety PLC.
FEATURES
- DO card type FBM242, 16 channels Digital Output board interface.
- 16 position Terminal Board for up to 16 channels.
- Lower cables installation and maintenance costs.
- Power supplies fault monitoring.
- Spare fuse provided.
- Additional terminals for load individual turn off.
- Additional terminals to interface a safety PLC for load switch off.
- Mounting hardware provided for: Wall mounting, M4 thread screw; Wall mounting, M4 self tapping screw; Single Din Rail mounting kit.
STATUS
CHANNELS
16