TBE-D5001-TRI-001 G.M. International s.r.l.
GM International

TBE-D5001-TRI-001

TBE-D5001-TRI-001
SIL3 HART® Mux Term. Board for Tricon AI Cards 3700, 3700A, 3721 and Tricon CX AI Card 3722X

This Termination Board with Enclosure (TBE) provides direct connection between the I/O Card of the system and 2-wire passive or active transmitters. At the same time, it makes available an interface for the remote monitoring of any HART®-compatible 4/20 mA field device. This is obtained by a locally mounted HART® Multiplexer Modem 5700 series and by terminal block connectors to access the loops. The single TBE-D5001-TRI-001 Termination Board supports 32 channels. Yet, it could be extended with additional units (up to 8) to manage all 256 channels available on the HART® Modem 5700 series. The Mux unit connects, via the RS-485 interface, to an external PC running an FDT-based software package (PACTware™, etc...) through a dedicated Device Type Manager (DTM). The PC can communicate with multiple Mux units, located on different boards, in a multi-drop RS-485 mode. The 24 Vdc Power Supply of the TBE is connected to two plug-in terminal blocks, for a redundant power supply.

FEATURES

  • SIL 3 / SC 3
  • HART® Multiplexing Board of up to 32 analog signals (extendable to 256)
  • Tricon AI Cards board interfaces up to 32 channels
  • Field terminals for 2-wire passive/active transmitters
  • On-board voltage/current protections against unintentional short circuits
  • 4/20 mA HART® loops isolated with dual capacitors (short circuit proof)
  • Double terminal to ease RS-485 cable multi-drop
  • Lower cables installation and maintenance costs
  • Redundant power supply
  • Mounting hardware provided for single DIN Rail mounting kit

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

32

Request a free and personalized quotation!

Technical Data


General

Number of positions 1 x HART® Multiplexer Modem 5700 series.
Maximum number of channels 32 on a single board, extendable to 256 with 8 boards and 1 HART® Multiplexer Modem 5700 series. Up to 16128 smart devices in full topology with 504 boards and 63 HART® Multiplexer Modem 5700 series.

Supply

Voltage 24 Vdc nom (20 to 30 Vdc), reverse polarity protected, double terminal blocks for redundant power supply, with OR diodes to mix supply voltages.
Current Consumption 44 mA @ 24 Vdc with full topology (8 boards) with no transmitters, typical.
Max allowed current consumption 1.5 A (as total supply).
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm².
Protection fuse 2 A time lag.

I/O Card Interface

Connection 2 x ELCO 8016, 56-poles receptacle connector (require male mating connector).
Cable system cable 4000189-5xx.

Field Interface

Connection by screw with terminations up to 2.5 mm².
Max supply current per channel 50 mA (resettable fuse protected).
Signal current range 0 to 25 mA.

Serial Interface

Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm².
Protocol HART® over RS-485.

Additional TBs interface

Connection 2 x flat cable 10 poles male connectors (requires female mating connector).
Cable flat cables CABF022, CABF023, CABF024.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Max altitude 2000 m a.s.l.
Storage temperature temperature limits –45 to +80 °C.

Mounting

Type Hardware included for mounting on single DIN-rail 35 mm.
Weight about 778 g (+ 50 g plastic clips or 380 g metal clips).
Location installation in Safe Area.
Dimensions Width 235 mm, Depth 135 mm, Height 154 mm.

Data Sheet


Datasheet of TBE-D5001-TRI-001 ( EN )
Schneider Tricon TB Summary ( EN )
Schneider Tricon CX TB Summary ( EN | ES | FR | CN | JA | PT | IT | DE | RU )

Instruction Manual


Instruction Manual of termination board HART for Tricon and Tricon CX systems ( EN )
Instruction Manual for installation of TBE-FIX-MT-xxx (valid for TBE-HRT & TBE-TRI & TBE-GMI) ( EN )
Instruction Manual for installation of TBE-FIX-PL-001 (valid for TBE-HRT & TBE-TRI & TBE-GMI) ( EN )
Safety Manual 5700 or 5700-110 + TBE-D5001-HRT-003, -004, -005, -006, -007 or TBE-D5001-TRI-001 ( EN )

Certifications


Type Description Area Number Issued by Issue Date
EMC 5700 and TB EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.PA08.B.82359/24 CONTROL 2024-09-26
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
SIL TUV C-IS-272994-01 SIL Certificate Summary ( EN ) International C-IS-272994-01 TUV_SUD 2022-10-14

Declarations of Conformity


EU Declaration Termination Boards TB, TBE, TUE ( EN )
Declaration of Conformity G3 compliance ( EN )

Dimensions


Image of TBE-D5001-TRI-001_size

Connections