X1-IS-AO-01-S G.M. International s.r.l.
GM International

X1-IS-AO-01-S
I.S. SIL3 HART® Isolating Driver

The Isolating Driver X1-IS-AO-01 module is a high integrity analog output interface suitable for applications requiring SIL 3 level in safety related systems for high risk industries. It isolates and transfers a 4-20 mA signal from a controller located in Safe Area to a load in Hazardous Area. The circuit allows bi-directional communication signals, for HART® smart positioners. Line and load open/short circuit detection is provided: the fault in the field is directly mirrored to the PLC AO card as open circuit and it is also reported on the common fault line. To ease maintenance operations, field devices can be disconnected through a two-position insertion/extraction mechanism. This product requires a dedicated Termination Board.

FEATURES

  • SIL 3 / SC 3
  • Input from Zone 0 / Division 1
  • Installation in Zone 2 / Division 2
  • Loop disconnection to ease maintenance operations
  • HART® compatible
  • Line & Load short/open circuit programmable diagnostics
  • Out-of-range fault with programmable thresholds
  • Field fault mirroring to the DCS/PLC IO Card
  • High Accuracy
  • Three port isolation, Input/Output/Supply

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

1

Request a free and personalized quotation!

Technical Data


General

Power Dissipation 0.75 W @ 24 Vdc with 20 mA on I/P output, typical.

System Supply

Voltage 24 Vdc nom (18 to 30 Vdc).
Current Consumption 30 mA @ 24 Vdc with 20 mA on I/P output, typical.

System In

Type Current 4 to 20 mA.
Input fault impedance 16 kΩ @ 24 Vdc (input current 1.5 mA), typical.

Field Out

Type Current 4 to 20 mA + HART.
Maximum load 600 Ω.
Response time 5 ms.

Fault

Type Load short/open with settable limits on voltage, current and resistance.
Fault signalling common fault & fault mirroring on DCS/PLC IO.

Performance

Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C Tamb.
Calibration accuracy ≤ ±20 µA.
Linearity accuracy ≤ ±20 µA.
Temp. influence ≤ ±2 µA/°C.

Isolation

Test Voltage Field Out/System In 2.5 kV; Field Out/System Supply 2.5 kV; System In/System Supply 500 V.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Storage temperature temperature limits –45 to +80 °C.

Safety description

Equipment Associated apparatus and non-sparking electrical equipment.
Safety parameters Uo = 26.7 V, Io = 92 mA, Po = 610 mW at terminals A-Z. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C.

Mounting

Type On custom Termination Board.
Weight about 50 g.
Dimensions Width 10 mm, Depth 80 mm, Height 120 mm.

Data Sheet


Datasheet of X1-IS-AO-01 ( EN )

Instruction Manual


Instruction Manual of X1-IS-AO-01 ( EN )
FM Control Drawing of X1-IS-AO-01 ( EN )
Safety Information of X1-IS-AO-01-S ( EN )

Certifications


Type Description Area Number Issued by Issue Date
ATEX FM ATEX I.S. X1 Series English Certificate ( EN ) Europe FM23ATEX0038X FM 2025-01-13
Ex FM US X1 Series Divisions and Zones English Certificate ( EN ) North America FM23US0073X FM 2025-01-09
Ex FM Canada X1 Series Divisions and Zones English Certificate ( EN ) North America FM23CA0055X FM 2025-01-09
IECEx FM IECEx X1 Series English Certificate ( EN ) International IECEx FMG 23.0018X FM 2025-01-09
UKEx FM UKEx I.S. X1 Series English Certificate ( EN ) United Kingdom FM23UKEX0039X FM 2025-01-15

Dimensions


Image of X_size

Connections