X1-IS-DO-02-S G.M. International s.r.l.
GM International

X1-IS-DO-02-S
I.S. SIL3 Digital Output Driver with Diagnostics

The Digital Output Driver X1-IS-DO-02 module is suitable for energizing safety related circuits, up to SIL 3 level, for high risk industries. It can drive solenoid valves, visual or audible alarms to alert a plant operator, or other process control devices in Hazardous Area from control signals located in Safe Area. They can also be used as switchable supplies to power measuring or process control equipments. On the field side, the three most widespread Intrinsic Safety valve family parameters are supported. On the system side, a wide compatibility towards different DCS/PLC is guaranteed: driving pulse testing is permitted by a dedicated internal circuit, which prevents spurious activations and LED flickering, while offering an acceptable resistance to the DO Card. Line and load short/open circuit detection are provided, both when the load is off and when the load is on. The fault in the field is directly mirrored to the PLC DO by artificially increasing the input impedance without changing the output state, and it is also reported to the cumulative fault. To ease maintenance operations, field devices can be disconnected through a two-position insertion/extraction mechanism. This product requires a dedicated Termination Board.

FEATURES

  • SIL 3 / SC 3
  • Input from Zone 0 / Division 1
  • Installation in Zone 2 / Division 2
  • Loop disconnection to ease maintenance operations
  • Short-circuit proof
  • Three different IS valve family parameters supported
  • Compatible with DCS/PLC pulse testing
  • Selectable input impedance (software programmable)
  • Line & Load short/open circuit detection (programmable thresholds)
  • Field fault mirroring to the DCS/PLC DO Card
  • Three port isolation, Input/Output/Supply

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

Request a free and personalized quotation!

Technical Data


General

Power Dissipation 1.5 W/1.25 W @ 24 Vdc with 40 mA/30 mA Field Out C (maximum dissipation), 24 Vdc System In, typical.

System Supply

Voltage 24 Vdc nom (18 to 30 Vdc).
Current Consumption 70 mA, @ 24 Vdc with 40 mA Field Out, typical.

System In

Type 24 Vdc nom (18 to 30 Vdc).
Current Consumption 12 mA @ 24 Vdc, typical.
Input impedance 2 kΩ, typical.

Field Out

Type Power supply with three different output characteristics, Out A, Out B and Out C.
Max working current 40 mA (up to 60 °C for any output). Out A: linear derating from 40 mA (60 °C) down to 35 mA (70 °C). Out B/C: linear derating from 40 mA (60 °C) down to 30 mA (70 °C).
Short circuit current 45 mA, typical.
Response time 50 ms.
Output typical characteristics

Fault

Type Load & line short/open circuit.
Line/load fault programmable resistance (20 Ω to 20 kΩ), current (1 mA to 40 mA) and voltage (100 mV to 24 V) limits.
Fault signalling common fault & fault mirroring on DCS/PLC DO.
Response time ≤ 1 s.

Isolation

Test Voltage Field Out/System In 2.5 kV; Field Out/System Supply 2.5 kV; System In/System Supply 500 V.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Storage temperature temperature limits –45 to +80 °C.

Safety description

Equipment Associated apparatus and non-sparking electrical equipment.
Safety parameters Uo = 25.8 V, Io = 145 mA, Po = 932 mW at terminals A-Z (Out A). Uo = 25.8 V, Io = 112 mA, Po = 715 mW at terminals B-Z (Out B). Uo = 25.8 V, Io = 96 mA, Po = 612 mW at terminals C-Z (Out C). Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C.

Mounting

Type On custom Termination Board.
Weight about 50 g.
Dimensions Width 10 mm, Depth 80 mm, Height 120 mm.

Data Sheet


Datasheet of X1-IS-DO-02-S ( EN )

Instruction Manual


Instruction Manual of X1-IS-DO-02 ( EN )
FM Control Drawing of X1-IS-DO-02 ( EN )
Safety Information of X1-IS-DO-02-S ( EN )

Certifications


Type Description Area Number Issued by Issue Date
ATEX FM ATEX I.S. X1 Series English Certificate ( EN ) Europe FM23ATEX0038X FM 2025-01-13
Ex FM US X1 Series Divisions and Zones English Certificate ( EN ) North America FM23US0073X FM 2025-01-09
Ex FM Canada X1 Series Divisions and Zones English Certificate ( EN ) North America FM23CA0055X FM 2025-01-09
IECEx FM IECEx X1 Series English Certificate ( EN ) International IECEx FMG 23.0018X FM 2025-01-09
UKEx FM UKEx I.S. X1 Series English Certificate ( EN ) United Kingdom FM23UKEX0039X FM 2025-01-15

Declarations of Conformity


EU Declaration of Conformity of X1-IS-DO-02 ( EN | IT )
UK Declaration of Conformity of X1-IS-DO-02 ( EN )

Dimensions


Image of X_size

Connections