D1073S

1 Ch, Universal Temp. Converter and Trip Amplifier, SIL 2

Descrizione

The single channel DIN Rail Temperature Signal Converter and Trip Amplifier D1073S accepts a low level dc signal from millivolt, thermocouple or RTD temperature sensor, located in Hazardous Area, and converts, with isolation, the signal to drive a Safe Area load. Output signal can be direct or reverse. Two independent Alarm Trip Amplifiers are also provided. Each alarm energizes, or de-energizes, an SPST relay for high, low, low-startup or burnout alarm functions. The two alarm relays trip points are settable over the entire input signal range.

Caratteristiche

• Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
• mV, thermocouples, RTD or transmitting potentiometers Input Signal.
• Programmable RTD line resistance compensation.
• Reference Junction Compensation automatic or fixed (programmable value).
• 0/4-20 mA, 0/1-5 V, 0/2-10 V Output Signal temperature linear or reverse.
• 16 characters tag.
• Two independent trip amplifiers.
• Output for burnout detection.
• Common burnout detection available when using Power Bus enclosure.
• High Accuracy, μP controlled A/D converter.
• Three port isolation, Input/Output/Supply.
• EMC Compatibility to EN61000-6-2, EN61000-6-4.
• Fully programmable operating parameters.
• Simplified installation using standard DIN Rail and plug-in terminal blocks.
• 250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.

Alimentazione

24 Vdc nom (20 to 30 Vdc)

Canali

1

Livello SIL

SIL 2
D1073S - SIL 2 Temperature Signal Converter and Trip Amplifiers

richiesta di quotazione

Download

    DTS0043 D1073S specifiche (English) (PDF 351 KB)
    ISM0019D1073S Istruzioni (PDF 830 KB)
    ISM0062Manual Configuration Table (PDF 76 KB)
    ISM0102General D1000 Series Instruction Manual (PDF 2.39 MB)
    ISM0142UL Control Drawing for D1073S (PDF 126 KB)
    ISM0182Potentiometer configuration (PDF 116 KB)
    ISM0155General D1000 Series Safety Instruction Manual (PDF 4.62 MB)
    CRT003Certificato ATEX n. DMT 01 ATEX E 042 X (I.S.) (PDF 10.99 MB)
    CRT014Certificato Metrologico per serie D1000 (Russia) (PDF 779 KB)
    CRT018Analisi EXIDA SIL2 SIL3 (04/10-27) (PDF 390 KB)
    CRT020FM 3024643 (USA) & FM-C 3029921C (Canada) (PDF 3.42 MB)
    CRT028Certificato Korean Register Type Approval (PDF 245 KB)
    CRT032CoC IECEx per serie D1000 (I.S.) [link IECEx BVS 07.0027X] (PDF 2.80 MB)
    CRT047Certificato ATEX n. IMQ 09 ATEX 013 X (non scintillante) (PDF 364 KB)
    CRT125CoC IECEx per serie D1000 (non scintillante) [link IECEx IMQ 13.0011X] (PDF 191 KB)
    CRT142TÜV SIL Certificate Summary (PDF 919 KB)
    CRT175INMETRO Certificate DNV 13.0108X (PDF 843 KB)
    CRT179Certificato DNV per gli standard navali e offshore (serie D1000) (PDF 2.06 MB)
    CRT192TRCU Certificate for D1000 Series (PDF 3.15 MB)
    CRT216Ukraine certificate for D1000 series (PDF 3.50 MB)
    CRT293UL-cUL D1052, D1053, D1072, D1073 Divisions and Zones (PDF 467 KB)
    APN0005D1052-53, D1072-73 Signal Converter DIN Rail (PDF 25 KB)
    APN0006D1070, D1072, D1073 Signal Converter DIN Rail (PDF 29 KB)
    APN0007Universal AC Power Supply for Series D1000 (PDF 44 KB)
    APN0012D1070,D1072,D1073 Signal Converter DIN Rail (PDF 29 KB)
    SWC1090D1000 and E1000 Software Configurator for Windows
    BUSContenitore opzionale con alimentazione a Bus
    MCHP065Din Rail Anchor, for Terminal Block Side of Bus Power
    MOR016DIN Rail End Stopper Terminal Block
    MOR017Plug-in Terminal Block male, Horizontal Output, for Bus Power
    MOR022Plug-in Terminal Block female, Horizontal Output, for Bus Power
    OPT1091Cold Junction Compensator Required for TC Inputs
    PPC1090Pocket Portable Configurator for D105* D106* D107*
    PPC1092D1000 Series Serial Adapter Configurator.
    USBADAPTRS-232 to USB Adapter.
Siete interessati a questo prodotto? Richiesta di quotazione, ricerca un esperto oppure contattateci.

« Previous: D1072S
D1073S
Next: D1080D »