D6020D

SIL 2 Powered Isolating Driver Hart

Description

The dual channel Isolating Driver D6020D module is a high integrity analog output interface suitable for applications requiring SIL 2 level (according to IEC 61508:2010 Ed. 2) in safety related systems for high risk industries.
It isolates and transfers a 4-20 mA signal from a controller to a load up to 700 Ω. It has a high output capacity of 15 V at 20 mA combined with a low drop across its input terminals.
The circuit allows bi-directional communication signals, for Hart positioner.
In the 4-20 mA input range, a field open or short circuit, reflects a high impedance to the control device circuit and actuates (de-energizes) the channel fault output transistor and actuates (energizes) the cumulative fault output available on Power Bus connector.
A fault output signal for each channel is available when mounted on customized Termination Board. In addition the single channel D6020S provides open collector transistor output on terminal blocks.
Short circuit fault detection can be enabled (two different levels can be selected) or disabled via DIP-Switch programming.
Mounting on standard DIN-Rail, with or without Power Bus, or on customized Termination Boards.

Features

• Systematic capability SIL 3
• 2 fully independent channels.
• 4-20 mA Input, Output Signal.
• Hart compatible.
• Field open and short circuit detection and signaling for each channel and cumulative.
• High Accuracy.
• Three port isolation, Input/Output/Supply.
• EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
• In-field programmability by DIP Switch.
• High Density, two channels per unit.
• Simplified installation using standard DIN-Rail and plug-in terminal blocks, with or without Power Bus, or customized Termination Boards.

Supply

18-30 Vdc

Channels

2 (1 Channel: D6020S)

SIL level

SIL 2
D6020D - SIL 2 non I.S. Powered Isolating Driver Hart Compatible

Download

    DTS0461 D6020D data sheet (English) (PDF 298 KB)
    ISM0212D6020D instruction manual (PDF 529 KB)
    ISM0402D6020 safety manual (PDF 250 KB)
    CRT112Metrological Certificate for D5000/D6000 series (Russia) (PDF 9.10 MB)
    CRT130TÜV SIL Functional Safety Certificate (PDF 4.38 MB)
    CRT253Metrological Certificate for D5000/D6000 Series (Belarus) (PDF 1.80 MB)
    CRT303TÜV SIL Certificate Summary (PDF 4.58 MB)
    CRT323EAC EMC Declaration for D5000 and D6000 series (PDF 2.07 MB)
    JDFT04912mm DIN Rail Connector
    MCHP196Power Bus Terminal Block Cover and Fix
    MOR017Plug-in Terminal Block male, Horizontal Output, for Bus Power
    MOR022Plug-in Terminal Block female, Horizontal Output, for Bus Power

 

Request a quotation

« Previous: D6017SS
D6020D
Next: D6020S »