Supply |
Type
|
24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp.
|
Current Consumption
|
60 mA @24V with 20 mA output typical.
|
Power Dissipation
|
1.0 W with 24 V supply voltage and 20 mA output typical.
|
Max. power consumption
|
2.0 W at 30 V supply voltage and short circuit condition
|
Input |
Type
|
0/4 to 20 mA (separately powered input, voltage drop ≤ 0.9 V) or 4 to 20 mA (2 wire Tx current limited at ≈ 25 mA).
|
Transmitter line voltage
|
≥ 15.0 V at 20 mA with max. 20 mVrms ripple on 0.5 to 40 KHz frequency band.
|
Output |
Type
|
0/4 to 20 mA, on max. 600 Ω load in source mode; V min. 5 V at 0 Ω load V max. 30 V in sink mode, current limited at ≈ 23 mA or 0/1 to 5 V on internal 250 Ω shunt (or 0/2 to 10 V on internal 500 Ω shunt on request).
|
Response time
|
50 ms (10 to 90 % step change).
|
Output ripple
|
≤ 20 mVrms on 250 Ω communication load on 0.5 to 40 KHz band.
|
Frequency response
|
0.5 to 40 KHz bidirectional within 3 dB (HART® and higher frequency protocols).
|
Performance |
Ref. Conditions
|
24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
|
Calibration accuracy
|
≤ ± 0.1 % of full scale.
|
Linearity error
|
≤ ± 0.05 % of full scale.
|
Supply voltage influence
|
≤ ± 0.05 % of full scale for a min to max supply change.
|
Load influence
|
≤ ± 0.05 % of full scale for a 0 to 100 % load resistance change.
|
Temperature influence
|
≤ ± 0.01 % on zero and span for a 1 °C change.
|
Isolation |
Test Voltage
|
I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V.
|
Safety description |
Equipment
|
Associated apparatus and non-sparking electrical equipment
|
Safety parameters
|
Uo/Voc = 26.3 V, Io/Isc = 91 mA, Po/Po = 597 mW at terminals 14-15, 10-11. Uo/Voc = 1.1 V, Io/Isc = 38 mA, Po/Po = 11 mW at terminals 15-16, 11-12. Ui/Vmax = 30 V, Ii/Imax = 104 mA, Ci = 1.05 nF, Li = 0 nH at terminals 15-16, 11-12. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C.
|
Environmental conditions |
Operating temperature
|
temperature limits -20 to + 60 °C, relative humidity max 95 %.
|
Storage temperature
|
temperature limits -45 to + 80 °C.
|
Mounting |
Type
|
EN/IEC60715 TH 35 DIN-Rail.
|
Weight
|
about 125 g
|
Connection
|
by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm2.
|
Location
|
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
|
Protection class
|
IP 20.
|
Dimensions
|
Width 22.5 mm, Depth 99 mm, Height 114.5 mm.
|