Supply |
Voltage
|
24 Vdc nom (20 to 30 Vdc).
Reverse polarity protected, ripple within voltage limits ≤ 5 Vpp.
|
Current Consumption
|
60 mA with 20 mA transducer consumption and
2 mA output load, typical.
|
Power Dissipation
|
1.1 W with 24 V supply voltage, 20 mA transducer consumption
and 2 mA output load typical.
|
Max. power consumption
|
at 30 V supply voltage and short circuit condition, 1.9 W.
|
Input |
Type
|
0 V to -20 V (10 KΩ impedance at terminals 15-16).
|
3 wires sensor supply voltage
|
more than -21.0 V at 0 mA supply, more than -15.0 V at 20 mA supply
(current limited at ≈ 25 mA) at terminals 14-16.
|
2 wires sensor supply voltage
|
more than -15.0 V with constant current supply mode at terminals 15-16.
Supply current selectable at 4 mA, 6 mA or 10 mA (current supply mode enabled
connecting terminals 13-14, 4 mA with terminal 10 not connected,
6 mA connecting terminals 10-11 or 10 mA connecting terminals 10-12).
|
Output |
Type
|
0 to -20 V on 10 KΩ load, with 10 Ω output resistance.
|
Response time
|
10 µs (10 to 90 % step change).
|
Output ripple
|
≤ 20 mVrms on 0.5 to 20 KHz band.
|
Frequency response
|
DC to 10 KHz within 0.1 dB, 10 KHz to 20 KHz within 3 dB.
|
Performance |
Type
|
Ref. Conditions 24 V supply, 10 KΩ load, 23 ± 1 °C ambient temperature.
|
Calibration accuracy
|
≤ ± 0.05 % of full scale.
|
Linearity error
|
≤ ± 0.05 % of full scale.
|
Supply voltage influence
|
≤ ± 0.005 % of full scale for a min to max supply change.
|
Temperature influence
|
≤ ± 0.005 % on zero and span for a 1 °C change.
|
Isolation |
Test Voltage
|
I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; Out/Supply 500 V.
|
Environmental conditions |
Operating
|
temperature limits -20 to + 60 °C,
relative humidity max 90 % non condensing, up to 35 °C.
|
Storage
|
temperature limits – 45 to + 80 °C.
|
Safety description |
Safety parameters
|
Uo/Voc = 25.9 V, Io/Isc = 90 mA, Po/Po = 576 mW at terminals 14-16.
Uo/Voc = 1.1 V, Io/Isc = 12 µA, Po/Po = 4 µW at terminals 15-16;
Ui/Vmax = 30 V, Ci = 0 nF, Li = 1.5 µH at terminals 15-16
(when used with 3 wires transducer or 2 wires AC sensor connecting terminals 9-14).
Uo/Voc = 27 V, Io/Isc = 90 mA, Po/Po = 576 mW at terminals 15-16
(when used with 2 wire constant current supply mode connecting terminals 13-14).
Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C.
|
Mounting |
Type
|
EN/IEC60715 TH 35 DIN-Rail.
|
Weight
|
about 150 g.
|
Connection
|
by polarized plug-in disconnect screw terminal blocks to accomodate
terminations up to 2.5 mm2.
|
Location
|
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4,
Class I, Division 2, Groups A, B, C, D Temperature Code T4 and
Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
|
Protection class
|
IP 20.
|
Dimensions
|
Width 22.5 mm, Depth 99 mm, Height 114.5 mm.
|