| Supply | 
  
    
            
                | Voltage | 24 Vdc nom (20 to 30 Vdc) reverse polarity protected,
ripple within voltage limits ≤ 5 Vpp. | 
        
            
                | Current Consumption | 25 mA typical. | 
        
            
                | Power Dissipation | 0.6 W with 24 V supply voltage and fault relay energized, typical. | 
        
            
                | Max. power consumption | at 30 V supply voltage and fault relay energized, 0.9 W. | 
        
        
            | Input | 
  
    
            
                | Type | 24 Vdc nom (20.4 to 27.6 Vdc) reverse polarity protected. | 
        
            
                | Current Consumption | 50 mA with relay energized, typical. | 
        
            
                | Power Dissipation | 1.2 W with 24 V input voltage and relay energized, typical. | 
        
            
                | Max. power consumption | at 27.6 V input voltage and relay energized, 1.5 W. | 
        
        
            | Output | 
  
    
            
                | Type | voltage free relay contact, normally open. | 
        
            
                | Contact material | Ag Alloy (Cd free). | 
        
            
                | Contact rating | 3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W (resistive load). | 
        
            
                | Contact inrush current | 5 A at 30 Vdc, 250 Vac. | 
        
            
                | Contact min. switching current | 10 mA. | 
        
            
                | DC Load breaking capacity | See Instruction Manual | 
        
            
                | Mechanical / electrical life | 50 * 106 / 1 * 105 operation, typical. | 
        
            
                | Operate / release time | 5 / 3 ms typical. | 
        
            
                | Bounce time NO / NC contact | 3 ms. | 
        
            
                | Frequency response | 10 Hz maximum. | 
        
        
            | Fault detection | 
  
    
            
                | De-energized fault signal | ≤ 100 μA continuous (typical 65 μA). | 
        
            
                | De-energized open output detection | load resistance ≥ 350 KΩ (current ≤ 30 μA). | 
        
            
                | De-energized no fault detection | load resistance ≤ 250 KΩ | 
        
            
                | Energized open output detection | load current ≤ 10 mA (no fault detection ≥ 25 mA). | 
        
            
                | Fault signalling | voltage free NE SPST relay contact
(output de-energized in fault condition). | 
        
            
                | Contact rating | 3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W (resistive load). | 
        
            
                | Response time | 200 ms typical. | 
        
        
            | Isolation | 
  
    
            
                | Test Voltage | Output/Input 2.5 KV; Output/Supply 2.5 KV; Output/Fault Output 2.5 KV;
Input/Supply 500 V; Input/Fault Output 500 V; Fault Output/Supply 500 V. | 
        
            
                | Storage | temperature limits –20 to + 60 °C, relative humidity max 95 %. | 
        
        
            | Environmental conditions  | 
  
    
            
                | Operating | temperature limits –20 to + 60 °C, relative humidity max 95 %. | 
        
            
                | Storage | temperature limits - 45 to + 80 °C. | 
        
            
                | Connection | about 155 g. | 
        
            
                | Location | by polarized plug-in disconnect screw terminal blocks to accomodate
terminations up to 2.5 mm2. | 
        
            
                | Protection class | Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4,
Class I, Division 2, Groups A, B, C, D Temperature Code T4 and
Class I, Zone 2, Group IIC, IIB, IIA T4 installation. | 
        
            
                | Dimensions | IP 20. | 
        
        
            | Mounting | 
  
    
            
                | Type | EN/IEC60715 TH 35 DIN-Rail. | 
        
            
                | Weight | about 155 g. | 
        
            
                | Connection | by polarized plug-in disconnect screw terminal blocks to accomodate
terminations up to 2.5 mm2. | 
        
            
                | Location | Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4,
Class I, Division 2, Groups A, B, C, D Temperature Code T4 and
Class I, Zone 2, Group IIC, IIB, IIA T4 installation. | 
        
            
                | Protection class | IP 20. | 
        
            
                | Dimensions | Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |