Supply |
Voltage
|
24 Vdc nom (20 to 30 Vdc) reverse polarity protected,
ripple within voltage limits ≤ 5 Vpp.
|
Current Consumption
|
25 mA typical.
|
Power Dissipation
|
0.6 W with 24 V supply voltage and fault relay energized, typical.
|
Max. power consumption
|
at 30 V supply voltage and fault relay energized, 0.9 W.
|
Input |
Type
|
24 Vdc nom (20.4 to 27.6 Vdc) reverse polarity protected.
|
Current Consumption
|
50 mA with relay energized, typical.
|
Power Dissipation
|
1.2 W with 24 V input voltage and relay energized, typical.
|
Max. power consumption
|
at 27.6 V input voltage and relay energized, 1.5 W.
|
Output |
Type
|
voltage free relay contact, normally open.
|
Contact material
|
Ag Alloy (Cd free).
|
Contact rating
|
3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W (resistive load).
|
Contact inrush current
|
5 A at 30 Vdc, 250 Vac.
|
Contact min. switching current
|
10 mA.
|
DC Load breaking capacity
|
See Instruction Manual
|
Mechanical / electrical life
|
50 * 106 / 1 * 105 operation, typical.
|
Operate / release time
|
5 / 3 ms typical.
|
Bounce time NO / NC contact
|
3 ms.
|
Frequency response
|
10 Hz maximum.
|
Fault detection |
De-energized fault signal
|
≤ 100 μA continuous (typical 65 μA).
|
De-energized open output detection
|
load resistance ≥ 350 KΩ (current ≤ 30 μA).
|
De-energized no fault detection
|
load resistance ≤ 250 KΩ
|
Energized open output detection
|
load current ≤ 10 mA (no fault detection ≥ 25 mA).
|
Fault signalling
|
voltage free NE SPST relay contact
(output de-energized in fault condition).
|
Contact rating
|
3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W (resistive load).
|
Response time
|
200 ms typical.
|
Isolation |
Test Voltage
|
Output/Input 2.5 KV; Output/Supply 2.5 KV; Output/Fault Output 2.5 KV;
Input/Supply 500 V; Input/Fault Output 500 V; Fault Output/Supply 500 V.
|
Storage
|
temperature limits –20 to + 60 °C, relative humidity max 95 %.
|
Environmental conditions |
Operating
|
temperature limits –20 to + 60 °C, relative humidity max 95 %.
|
Storage
|
temperature limits - 45 to + 80 °C.
|
Connection
|
about 155 g.
|
Location
|
by polarized plug-in disconnect screw terminal blocks to accomodate
terminations up to 2.5 mm2.
|
Protection class
|
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4,
Class I, Division 2, Groups A, B, C, D Temperature Code T4 and
Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
|
Dimensions
|
IP 20.
|
Mounting |
Type
|
EN/IEC60715 TH 35 DIN-Rail.
|
Weight
|
about 155 g.
|
Connection
|
by polarized plug-in disconnect screw terminal blocks to accomodate
terminations up to 2.5 mm2.
|
Location
|
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4,
Class I, Division 2, Groups A, B, C, D Temperature Code T4 and
Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
|
Protection class
|
IP 20.
|
Dimensions
|
Width 22.5 mm, Depth 99 mm, Height 114.5 mm.
|