D1130D G.M. International s.r.l.
GM International

D1130D
SIL 2 Switch/Proximity Detector Repeater Relay Output DIN-Rail

The Switch/Proximity Detector Repeater type D1130 is a DIN Rail unit with one or two independent channels. The unit can be configured for contact or proximity detector, NO or NC and for NE or ND SPDT relay output contact. Each channel enables a Safe Area load to be controlled by a switch, or a proximity detector, located in Hazardous Area. D1130D dual channel type has two independent input channels and actuates the corresponding output relay. Two actuation modes can be independently DIP switch configured on each input channel: NO input/NE relay or NO input/ND relay. Contact or proximity sensor and its connection line short or open circuit fault detection is also DIP switch configurable: fault detection can be enabled (in case of fault it de-energizes the corresponding output relay and turns the fault LED on) or disabled (in case of fault the corresponding output relay repeats the input line open or closed status as configured). D1130S single channel type has one input channel and two output relays; the unit has two DIP switch configurable operating modes: Mode A) input channel actuates in parallel the two output relays (DPDT contact). Relay actuation mode can be independently configured for each output in two modes: NO input/NE relay or NO input/ND relay. Mode B) input channel actuates output relay A configurable in two modes as in mode A above. Output relay B operates as a fault output (in case of input fault, relay B actuates and the fault LED turns on while relay A repeats the input line as configured). Actuation can be DIP switch configured in two modes: No input fault/energized relay (it de-energizes in case of fault) or No input fault/de-energized relay (it energizes in case of fault).

FEATURES

  • SIL2/SC2
  • Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
  • Universal AC supply voltage (85 to 250 Vac, 48 to 400 Hz).
  • NO/NC contact/proximity Detector Input.
  • Two SPDT Relay Output Signals.
  • SPDT Relay Output for fault detection on single channel version.
  • Three port isolation, Input/Output/Supply.
  • EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1.
  • In-field programmability by DIP Switch.
  • High Density, two channels per unit.
  • 250 Vrms (Um) max. voltage allowed to the Instruments associated with the barrier.

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

2

Request a free and personalized quotation!

Technical Data


Supply

Voltage 115-230 Vac, 50-60 Hz nom (85 to 250 Vac, 48 to 400 Hz), ripple within voltage limits ≤ 10 Vpp, 500 mA time lag fuse and 275 Vrms transient voltage surge suppressor protected. Limit supply voltage to 250 Vrms for Instrinsic Safety applications.
Current consumption @ 115 Vac 25 mA with short input and relays energized.
Current consumption @ 230 Vac 15 mA with short input and relays energized.
Max. power consumption at 264 Vac supply voltage, short circuit input and relays energized, 2.0 W

Input switching current levels

Type ON ≥ 2.1 mA, OFF ≤ 1.2 mA, switch current ≈ 1.65 mA ± 0.2 mA hysteresis.
Fault current levels open fault ≤ 0.2 mA, short fault ≥ 6.8 mA (when enabled both faults actuate fault relay)
Input equivalent source 8 V 1 KΩ typical (8 V no load, 8 mA short circuit).

Output

Type voltage free SPDT relay contact.
Contact material AgCdO.
Contact rating 2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load).
DC Load breaking capacity See Instruction manual
Mechanical / electrical life 30 * 106 / 1 * 105 operation, typical.
Operate / release time 7 / 3 ms typical.
Bounce time NO / NC contact 3 / 5 ms.
Response time 20 ms.
Frequency response 10 Hz maximum.

Isolation

Test Voltage I.S. In/Out 2.5 KV; I.S. In/Supply 2.5 KV; Out/Supply 2.5 KV; Out/Out 2.5 KV.
Storage temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C.

Environmental conditions

Operating temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C.
Storage temperature limits – 45 to + 80 °C.

Safety description

Safety parameters Uo/Voc = 10.7 V, Io/Isc = 15 mA, Po/Po = 39 mW at terminals 13-14, 15-16. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C.
Weight EN/IEC60715 TH 35 DIN-Rail.
Connection about 145 g D1130D, 140 g D1130S.
Location by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2.
Protection class Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
Dimensions IP 20

Mounting

Type EN/IEC60715 TH 35 DIN-Rail.
Weight about 145 g
Connection by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2.
Location Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
Protection class IP 20
Dimensions Width 22.5 mm, Depth 99 mm, Height 114.5 mm.

Data Sheet


Datasheet of D1130 ( EN )
D1000 Series Common Specifications and Dimensional Drawing ( EN )

Instruction Manual


Instruction Manual D1130 ( EN )
Instruction Manual D1000 Series ( EN | RU )
Ex safety instruction manual for D1000 series ( EN | IT )
INMETRO safety instruction manual for D1000 series ( PT )
UL Control Drawing D1130 ( EN )

Certifications


Type Description Area Number Issued by Issue Date
ATEX DEKRA ATEX D1000 Series English Certificate ( EN ) Europe DMT 01 ATEX E 042 X DEKRA 2022-04-25
ATEX IMQ Zone 2 Applications D1000 Series Certificate ( EN ) Europe IMQ 09 ATEX 013 X IMQ 2022-05-03
EMC D1000 EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.НХ37.В.06311/20 EUROCERT 2020-08-13
Ex EAC Ex Certificate for D1000 Series ( RU ) Eurasian Community ЕАЭС RU С-IT.НА67.В.00113/20 TECHNOPROGRESS 2020-09-04
Ex UL-cUL D1030, D1031, D1130 Divisions and Zones ( EN ) North America 20130115-E222308 UL 2013-01-15
Ex FM No.3024643-3029921C Certificate ( EN ) North America 3024643-3029921C FM 2005-12-16
Ex INMETRO Certificate DNV 13.0108 X for D1000 series ( EN ) Brazil DNV 13.0108 X DNV 2022-12-10
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
IECEx IMQ IECEx Zone 2 Applications D1000 Series Certificate ( EN ) International IECEx IMQ 13.0011X IMQ 2022-05-03
IECEx DEKRA IECEx for D1000 Series ( EN ) International IECEx BVS 07.0027X DEKRA 2022-05-30
Maritime KR Maritime Certificate D1000 Series ( EN ) International MIL20769-EL001 KR 2022-07-04
Maritime DNV Maritime Certificate TAA00002BM for D1000 Series ( EN ) International TAA00002BM DNV-GL 2024-04-05
SIL TUV C-IS-722238330 SIL Declaration of Compliance Summary ( EN ) International C-IS-722238330 TUV_SUD 2024-01-19

Declarations of Conformity


EU Declaration of Conformity D1000 series ( EN | IT )
EU Declaration of Conformity for D1000 series (zone 2) ( EN | IT )
EU Declaration of Conformity for RoHS, ASBESTOS. ( EN )
Declaration of G3 compliance for D1000_PSD1000-PSD1001-PSD1001C-PSD1004-PSD1220-PSD1220-098 SERIES ( EN )

Dimensions


Image of D1130S/D1130D_size

Connections


Drawings


2d_drawing_D1000_dwg ( EN )
3d_drawing_D1000_dwg ( EN )
3d_drawing_D1000_stp ( EN )

RELATED PRODUCTS