X1-NIS-DI-02-S G.M. International s.r.l.
GM International

X1-NIS-DI-02-S
SIL2 Switch/Proximity Transistor-Out Repeater

The Switch/Proximity Detector Repeater X1-NIS-DI-02 is a module suitable for applications requiring SIL 2 level in safety related systems for high risk industries. The unit can be configured for switches or proximity detectors, and repeats the input state to an open-collector transistor in Safe Area. The selectable fault detection circuit is available for proximity sensors or switches equipped with end-of-line resistors. When selected, the fault drives the common line and may also force the output open, if required. Input to output function can be inverted. To ease maintenance operations, field devices can be disconnected through a two-position insertion/extraction mechanism. This product requires a dedicated Termination Board.

FEATURES

  • SIL 2 / SC 3
  • Installation in Zone 2 / Division 2
  • Loop disconnection to ease maintenance operations
  • High frequency transistor output
  • Field open and short circuit detection (software programmable)
  • Inverted output available (software programmable)
  • Three port isolation, Input/Output/Supply

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

CHANNELS

1

Request a free and personalized quotation!

Technical Data


General

Power Dissipation 0.4 W @ 24 Vdc with short circuit input and 100 mA output current, typical.

System Supply

Voltage 24 Vdc nom (18 to 30 Vdc).
Current Consumption 13 mA @ 24 Vdc with short circuit input and closed output, typical.

System Out

Type Voltage free SPST optocoupled open-collector transistor. System Out dependence on Field In and fault is programmable through software.
Max voltage 35 Vdc.
Max current 50 mA.
Max voltage drop 1.5 V @ 50 mA.
Leakage current ≤ 50 μA @ 35 Vdc.
Response time ≤ 1 ms.
Frequency response 500 Hz maximum.

Field In

Type Voltage source according to NAMUR standard.
Input equivalent source 8 V/1 kΩ typical (8 V no load, 8 mA short).
Input switching current levels ON ≥ 2.1 mA, OFF ≤ 1.2 mA.
No Fault input current ≥ 0.35 mA and input resistance ≥ 360 Ω.
Open Fault input current ≤ 0.05 mA.
Short fault input resistance ≤ 100 Ω.

Fault

Type Field sensor fault is available on the common fault line, when input diagnostics is active.

Isolation

Test Voltage Field In/System Out 2.5 kV; Field In/System Supply 2.5 kV; System Out/System Supply 500 V.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Storage temperature temperature limits –45 to +80 °C.

Mounting

Type On custom Termination Board.
Weight about 55 g.
Dimensions Width 10 mm, Depth 80 mm, Height 120 mm.

Data Sheet


Datasheet of X1-NIS-DI-02 ( EN )

Instruction Manual


Safety Information of X1-NIS-DI-02-S ( EN )
Instruction Manual of X1-NIS-DI-02 ( EN )

Certifications


Type Description Area Number Issued by Issue Date
ATEX FM ATEX zone 2 X1 Series English Certificate ( EN ) Europe FM23ATEX0039X FM 2025-01-13
Ex FM US X1 Series Divisions and Zones English Certificate ( EN ) North America FM23US0073X FM 2025-01-09
Ex FM Canada X1 Series Divisions and Zones English Certificate ( EN ) North America FM23CA0055X FM 2025-01-09
IECEx FM IECEx X1 Series English Certificate ( EN ) International IECEx FMG 23.0018X FM 2025-01-09
UKEx FM UKEx zone 2 X1 Series English Certificate ( EN ) United Kingdom FM23UKEX0040X FM 2025-01-15

Declarations of Conformity


EU Declaration of Conformity of X1-NIS-DI-02 ( EN | IT )
UK Declaration of Conformity of X1-NIS-DI-02 ( EN )

Dimensions


Image of X_size

Connections