X1-NIS-RLO/SS-04-S G.M. International s.r.l.
GM International

X1-NIS-RLO/SS-04-S

X1-NIS-RLO/SS-04-S
SIL3 Solid-State Relay Out Module for 2A NE Loads with Diagnostics

The X1-NIS-RLO/SS-04 solid-state relay module is suitable for switching safety related circuits, up to SIL 3 level, for high risk industries. It provides isolation between input coils and output contacts, making available a safety NO contact for Normally Energized (NE) loads. A wide compatibility towards different DCS/PLC is guaranteed: driving pulse testing is permitted by a dedicated internal circuit, which prevents contact and LED flickering, while offering an acceptable resistance to the DO Card. Line and load short/open circuit detection with programmable limits and load voltage monitoring are provided, both when the load is off and when the load is on. The fault in the field is directly mirrored to the PLC DO by artificially increasing the input impedance without commuting the relay contacts, and it is also reported to the cumulative fault. To ease maintenance operations, field devices can be disconnected through a two-position insertion/extraction mechanism. This product requires a dedicated Termination Board.

FEATURES

  • SIL 3 / SC 3
  • Installation in Zone 2 / Division 2
  • Loop disconnection to ease maintenance operations
  • Up to 2 A functional / 6 A inrush current
  • Compatible with DCS/PLC pulse testing
  • Load disconnection on both supply lines available
  • Line & Load short/open circuit detection (programmable thresholds)
  • Load voltage monitoring
  • Field fault mirroring to the DCS/PLC DO Card
  • Automatic TProof test available through Gateway
  • Three port isolation, Input/Output/Supply

STATUS

 
   ACTIVE
Product lifecycle policy (EN)

Request a free and personalized quotation!

Technical Data


General

Power Dissipation 0.8 W @ 24 Vdc System Supply, with 2 A load current, typical.

System Supply

Voltage 24 Vdc nom (18 to 30 Vdc).
Current Consumption 18 mA @ 24 Vdc and relay energized, typical.

System In

Type 24 Vdc nom (18 to 30 Vdc).
Current Consumption 12 mA @ 24 Vdc, typical.
Input impedance 2 kΩ @ 24 Vdc, typical.

Field Supply

Type DC voltage supply.
Voltage range 0 to 60 Vdc.

Field Out

Type NE load.
Max ratings 2 A 60 Vdc 120 W.
Max inrush current 6 A.
Operate / release time 30 / 30 ms, typical.

Fault

Type Load & line short/open circuit, supply voltage monitoring.
Line/load fault programmable resistance (20 Ω to 20 kΩ) and current (20 mA to 2 A) limits.
Load supply voltage ok ≥ 20 Vdc.
Load supply voltage fault ≤ 5 Vdc.
Fault signalling common fault & fault mirroring on DCS/PLC DO.
Response time ≤ 1 s.

Isolation

Test Voltage Field Out/System In 2.5 kV; Field Out/System Supply 2.5 kV; System In/System Supply 500 V.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Storage temperature temperature limits –45 to +80 °C.

Mounting

Weight about 50 g.
Dimensions Width 10 mm, Depth 80 mm, Height 120 mm.

Data Sheet


Datasheet of X1-NIS-RLO/SS-04 ( EN )

Instruction Manual


Instruction Manual of X1-NIS-RLO/SS-04 ( EN )
Safety Information of X1-NIS-RLO/SS-04-S ( EN )
Safety Manual of X1-NIS-RLO/SS-04-S ( EN )

Certifications


Type Description Area Number Issued by Issue Date
ATEX FM ATEX zone 2 X1 Series English Certificate ( EN ) Europe FM23ATEX0039X FM 2025-01-13
Ex FM US X1 Series Divisions and Zones English Certificate ( EN ) North America FM23US0073X FM 2025-01-09
Ex FM Canada X1 Series Divisions and Zones English Certificate ( EN ) North America FM23CA0055X FM 2025-01-09
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
IECEx FM IECEx X1 Series English Certificate ( EN ) International IECEx FMG 23.0018X FM 2025-01-09
SIL TUV IT 25 SIL 0531 A SIL Certificate Summary ( EN ) International TUV IT 25 SIL 0531 A TUV_SUD 2025-01-29
UKEx FM UKEx zone 2 X1 Series English Certificate ( EN ) United Kingdom FM23UKEX0040X FM 2025-01-15

Declarations of Conformity


EU Declaration of Conformity of X1-NIS-RLO/SS-04 ( EN | IT )
UK Declaration of Conformity of X1-NIS-RLO/SS-04 ( EN )

Dimensions


Image of X_size

Connections