Supply |
Voltage
|
24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp.
|
Current Consumption
|
160 mA with 20 mA output typical.
|
Power Dissipation
|
2.3 W for 4 channels with 24 V supply voltage and 20 mA output typical.
|
Max. power consumption
|
at 30 V supply voltage, 4.0 W for 4 channels
|
Input |
Type
|
4 to 20 mA (2 wire Tx current limited at ≈ 22 mA).
|
Output |
Type
|
14.0 V typical at 20 mA with max. 30 mVrms ripple.
|
Response time
|
4 to 20 mA, on max. 300 Ω load source mode, current limited at 20.6 mA.
|
Output ripple
|
≤ 30 mVrms.
|
Performance |
Type
|
Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature
|
Calibration accuracy
|
≤ ± 0.1 % of full scale.
|
Linearity error
|
≤ ± 0.05 % of full scale.
|
Supply voltage influence
|
≤ ± 0.05 % of full scale for a min to max supply change.
|
Load influence
|
≤ ± 0.05 % of full scale for a 0 to 100 % load resistance change.
|
Temperature influence
|
≤ ± 0.01 % on zero and span for a 1 °C change.
|
Isolation |
Test Voltage
|
I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV.
|
Environmental conditions |
Operating
|
temperature limits -20 to + 60 °C, relative humidity max 95 %.
|
Storage
|
temperature limits - 45 to + 80 °C.
|
Safety description |
Safety parameters
|
Uo/Voc = 21.5 V, Io/Isc = 93 mA, Po/Po = 496 mW at terminals 13-14, 15-16, 9-10, 11-12.
Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C.
|
Mounting |
Type
|
EN/IEC60715 TH 35 DIN-Rail.
|
Weight
|
about 140 g.
|
Connection
|
by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm2.
|
Location
|
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
|
Protection class
|
IP 20.
|
Dimensions
|
Width 22.5 mm, Depth 99 mm, Height 114.5 mm.
|