Supply |
Type
|
12-24 Vdc nom (10 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp
|
Current Consumption
|
90 mA with 20 mA input/output and relays energized
|
Power Dissipation
|
1.7 W with 24 V supply, 20 mA input/output and relays energized.
|
Max. power consumption
|
at 30 V supply voltage, input short circuit, overload condition, relays energized and PPC1090 connected, 2.9 W.
|
Input |
Type
|
0/4 to 20 mA (separately powered input, voltage drop ≤ 1 V) or 4 to 20 mA (2 wire Tx current limited at ≈ 25 mA).
|
Integration time
|
100 ms
|
Resolution
|
1 µA.
|
Input range
|
0 to +22 mA
|
Transmitter line voltage |
Type
|
≥ 15.0 V at 20 mA with max. 20 mVrms ripple on 0.5 to 40 KHz frequency band.
|
Burnout |
Type
|
enabled or disabled. Analog output can be programmed to detect burnout condition with downscale or highscale forcing. Alarms can be programmed to detect burnout condition.
|
Range
|
low and high separated trip point value programmable between -5 to +25 mA.
|
Output |
Type
|
0/4 to 20 mA, on max. 600 Ω load source mode, current limited at 22 mA or 0/1 to 5 V or 0/2 to 10 V signal, limited at 11 V.
|
Resolution
|
1 µA current output or 1 mV voltage output.
|
Transfer characteristic
|
linear or reverse.
|
Response time
|
≤ 50 ms (10 to 90 % step change).
|
Output ripple
|
≤ 20 mVrms on 250 Ω communication load on 0.5 to 40 KHz band.
|
Frequency response
|
0.5 to 40 KHz bidirectional within 3 dB (HART® and higher frequency protocols) only with mA direct current output.
|
Alarm |
Trip point range
|
within rated limits of input sensor (see input for step resolution).
|
ON-OFF delay time
|
0 to 1000 s, 100 ms step, separate setting.
|
Hysteresis
|
0 to 5 mA (see input for step resolution).
|
Output
|
voltage free SPST relay contact.
|
Contact rating
|
2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load).
|
Performance |
Type
|
Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
|
Input
|
Calibration and linearity accuracy: ≤ ± 20 μA
Temperature influence: ≤ ± 1 μA of input for a 1 °C change.
|
Analog Output
|
Calibration accuracy: ≤ ± 0.1 % of full scale.
Output Linearity error: ≤ ± 0.05 % of full scale.
Supply voltage influence: ≤ ± 0.05% of full scale for min to max supply change
Load influence: ≤ ± 0.05% of full scale for 0 to 100 % load resistance change
Temperature influence: ≤ ± 0.01 % on zero and span for a 1 °C change.
|
Isolation |
Test Voltage
|
I.S. In/Outs 1.5 KV; I.S. In/Supply 1.5 KV; Analog Out/Supply 500 V; Analog Out/Alarm Outs 1.5 KV; Alarm Outs/Supply 1.5 KV; Alarm Out/Alarm Out 1.5 KV.
|
Environmental conditions |
Operating
|
temperature limits -20 to + 60 °C, relative humidity max 95 %.
|
Storage
|
temperature limits – 45 to + 80 °C.
|
Safety description |
Safety parameters
|
Uo/Voc = 26.3 V, Io/Isc = 91 mA, Po/Po = 597 mW at terminals 14-15.
Uo/Voc = 1.1 V, Io/Isc = 56 mA, Po/Po = 16 mW at terminals 15-16.
Ui/Vmax = 30 V, Ii/Imax = 128 mA, Ci = 1.05 nF, Li = 0 nH at terminals 15-16.
Um = 250 Vrms, -20 °C ≤ Ta ≤ 60°C.
|
Mounting |
Type
|
EN/IEC60715 TH 35 DIN-Rail.
|
Weight
|
about 175 g.
|
Connection
|
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2.
|
Location
|
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
|
Protection class
|
IP 20.
|
Dimensions
|
Width 22.5 mm, Depth 99 mm, Height 114.5 mm.
|