Supply |
Voltage
|
12-24 Vdc nom (10 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp.
|
Current Consumption
|
2 channels
|
Power Dissipation
|
70 mA with 20 mA output typical.
|
Max. power consumption
|
1.5 W with 24 V supply voltage and 20 mA output typical.
|
Input |
Type
|
0/4 to 20 mA (-4 to +24 mA reading) separately powered input,
voltage drop ≤ 0.5 V or 0/1 to 5 V or 0/2 to 10 V (-2 to +12 V reading) 1 MΩ impedance.
|
Integration time
|
100 ms.
|
Resolution
|
1 µA on current input, 1 mV on voltage input.
|
Visualization
|
1 µA on current input, 1 mV on voltage input.
|
Input range
|
-4 to +24 mA on current input, -2 to +12 V on voltage input.
|
Burnout |
Type
|
enabled or disabled. Analog output can be programmed to detect burnout condition with downscale or highscale forcing.
|
Range
|
low and high separated trip point value programmable between -5 to +25 mA on current input and -3 to +13 V on voltage input.
|
Output |
Type
|
0/4 to 20 mA, on max. 600 Ω load source mode, current limited at 22 mA or 0/1 to 5 V or 0/2 to 10 V signal, limited at 11 V.
|
Resolution
|
2 µA current output or 1 mV voltage output.
|
Transfer characteristic
|
linear or reverse.
|
Response time
|
≤ 50 ms (10 to 90 % step change).
|
Output ripple
|
≤ 20 mVrms on 250 Ω load.
|
Input performance |
Type
|
Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
|
Calibration and linearity accuracy
|
≤ ± 20 µA on current input or ≤ ± 10 mV on voltage input.
|
Temperature influence
|
≤ ± 2 µA, 1 mV of input for a 1 °C change.
|
Analog output performance |
Calibration accuracy
|
≤ ± 0.1 % of full scale.
|
Linearity error
|
≤ ± 0.05 % of full scale.
|
Supply voltage influence
|
≤ ± 0.05 % of full scale for a min to max supply change.
|
Load influence
|
≤ ± 0.05 % of full scale for a 0 to 100 % load resistance change
|
Temperature influence
|
≤ ± 0.01 % on zero and span for a 1 °C change.
|
Isolation |
Test Voltage
|
I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V.
|
Environmental conditions |
Operating
|
temperature limits -20 to + 60 °C, relative humidity max 95 %.
|
Storage
|
temperature limits -45 to + 80 °C.
|
Safety description |
Safety parameters
|
Uo/Voc = 10.8 V, Io/Isc = 4 mA, Po/Po = 11 mW at terminals 14-15-16, 10-11-12. Ui/Vmax = 30 V, Ci = 4.5 nF, Li = 0 nH at terminals 14-15-16, 10-11-12. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60°C.
|
Mounting |
Type
|
EN/IEC60715 TH 35 DIN-Rail.
|
Weight
|
at 30 V supply voltage, overload condition and
PPC1090 connected, 2.1 W
|
Connection
|
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2.
|
Location
|
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
|
Protection class
|
IP 20
|
Dimensions
|
Width 22.5 mm, Depth 99 mm, Height 114.5 mm.
|